Modbus communication Access to remote settings<br />

5/30<br />

ANSI 79 - Recloser function<br />

Function number: 1701<br />

Setting Data Format/Unit<br />

1 Recloser – enabled or disabled<br />

2 Recloser inhibition by input I26<br />

3 Number of cycles 1 to 4<br />

4 Recloser – disengaging time delay 10 ms<br />

5 Recloser – inhibition time delay 10 ms<br />

6 Reserved<br />

7 Cycle 1 – activation mode<br />

11<br />

8 Cycle 1 – isolation time delay 10 ms<br />

9 Reserved<br />

10 Cycle 2 – activation mode<br />

11<br />

11 Cycle 2 – isolation time delay 10 ms<br />

12 Reserved<br />

13 Cycle 3 – activation mode<br />

11<br />

14 Cycle 3 – isolation time delay 10 ms<br />

15 Reserved<br />

16 Cycle 4 – activation mode<br />

11<br />

17 Cycle 4 – isolation time delay 10 ms<br />

ANSI 81H - Overfrequency<br />

Function number: 1301<br />

Setting Data Format/Unit<br />

1 Enabled or disabled<br />

1<br />

2 Fs set point 0.1 Hz<br />

3 Tripping time delay 10 ms<br />

4 to 8 Reserved<br />

ANSI 81L - Underfrequency<br />

Function number: 14xx<br />

Relay 1: xx = 01<br />

Relay 2: xx = 02<br />

Setting Data Format/Unit<br />

1 Enabled or disabled<br />

1<br />

2 Fs set point 0.1 Hz<br />

3 Tripping time delay 10 ms<br />

4 to 8 Reserved<br />

ANSI 81R - Rate of change of frequency<br />

Function number: 1601<br />

Setting Data Format/Unit<br />

1 Enabled or disabled<br />

1<br />

2 dFs/dt set point 0.1 Hz/s<br />

3 Tripping time delay 10 ms<br />

4 to 8 Reserved<br />

1<br />

9<br />

PCRED301005EN - 06/<strong>20</strong>08