Commissioning Checking parameter<br />
and protection settings<br />
7/24<br />
Determination of parameter and protection settings<br />
All of the Sepam parameter and protection settings are determined beforehand by<br />
the design department in charge of the application, and should be approved by the<br />
customer.<br />
It is presumed that the study has been carried out with all the attention<br />
necessary, or even consolidated by a network coordination study.<br />
All of the Sepam parameter and protection settings should be available at the time of<br />
commissioning:<br />
b in hard copy format (with the SFT2841 software, the parameter and protection<br />
setting file for a Sepam can be printed directly or exported to a text file for editing)<br />
b and, when applicable, in the format of a file to be downloaded into Sepam using<br />
the SFT2841 software.<br />
Checking parameters and protection settings<br />
Check to be made when the Sepam parameter and protection settings have not been<br />
entered or downloaded during commissioning testing, to confirm the conformity of<br />
the parameter and protection settings entered with the values determined during the<br />
study.<br />
The aim of this check is not to confirm the relevance of the parameter and protection<br />
settings.<br />
1. Go through all the parameter and protection setting screens in the SFT2841<br />
software, in the order proposed in guided mode.<br />
2. For each screen, compare the values entered in the Sepam with the values<br />
recorded in the parameter and protection setting file.<br />
3. Correct any parameter and protection settings that have not been entered<br />
correctly, proceeding as indicated in the "Use of the (SFT2841) software" section of<br />
this <strong>manual</strong>.<br />
Conclusion<br />
Once the checking has been done and proven to be conclusive, as of that phase, the<br />
parameter and protection settings should not be changed any further and are<br />
considered to be final.<br />
In order to be conclusive, the tests which follow must be performed with these<br />
parameter and protection settings; no temporary modification of any of the values<br />
entered, with the aim of facilitating a test, is permissible.<br />
PCRED301005EN - 06/<strong>20</strong>08