7<br />

Commissioning Checking parameter<br />

and protection settings<br />

7/24<br />

Determination of parameter and protection settings<br />

All of the Sepam parameter and protection settings are determined beforehand by<br />

the design department in charge of the application, and should be approved by the<br />

customer.<br />

It is presumed that the study has been carried out with all the attention<br />

necessary, or even consolidated by a network coordination study.<br />

All of the Sepam parameter and protection settings should be available at the time of<br />

commissioning:<br />

b in hard copy format (with the SFT2841 software, the parameter and protection<br />

setting file for a Sepam can be printed directly or exported to a text file for editing)<br />

b and, when applicable, in the format of a file to be downloaded into Sepam using<br />

the SFT2841 software.<br />

Checking parameters and protection settings<br />

Check to be made when the Sepam parameter and protection settings have not been<br />

entered or downloaded during commissioning testing, to confirm the conformity of<br />

the parameter and protection settings entered with the values determined during the<br />

study.<br />

The aim of this check is not to confirm the relevance of the parameter and protection<br />

settings.<br />

1. Go through all the parameter and protection setting screens in the SFT2841<br />

software, in the order proposed in guided mode.<br />

2. For each screen, compare the values entered in the Sepam with the values<br />

recorded in the parameter and protection setting file.<br />

3. Correct any parameter and protection settings that have not been entered<br />

correctly, proceeding as indicated in the "Use of the (SFT2841) software" section of<br />

this <strong>manual</strong>.<br />

Conclusion<br />

Once the checking has been done and proven to be conclusive, as of that phase, the<br />

parameter and protection settings should not be changed any further and are<br />

considered to be final.<br />

In order to be conclusive, the tests which follow must be performed with these<br />

parameter and protection settings; no temporary modification of any of the values<br />

entered, with the aim of facilitating a test, is permissible.<br />

PCRED301005EN - 06/<strong>20</strong>08