Control and monitoring<br />
functions<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
Self-tests and fail-safe position<br />
Selecting the trip command and examples of<br />
use<br />
An analysis of the operational reliability of the whole installation should determine<br />
whether availability or safety of this installation should be prioritized if Sepam is in the<br />
fail-safe position. This information is used to determine the choice of trip command as<br />
outlined in the table below.<br />
CAUTION Selecting the trip command<br />
RISK OF UNPROTECTED INSTALLATION<br />
Diagram Control Event Trip Advantage Disadvantage<br />
Always connect the watchdog output to a<br />
1 Shunt trip breaker Sepam failure or No Availability of Installation not<br />
monitoring device when the selected trip<br />
or mechanical loss of the<br />
the installation protected until<br />
command does not result in the installation<br />
tripping when Sepam fails.<br />
latching contactor auxiliary power<br />
supply<br />
remedial<br />
intervention<br />
Failure to follow these instructions can cause<br />
equipment damage.<br />
(1)<br />
2 Breaker with<br />
undervoltage trip<br />
Sepam failure or Yes<br />
loss of the<br />
Safety of the<br />
installation<br />
Installation not<br />
available until<br />
coil (fail-safe) auxiliary power<br />
remedial<br />
supply<br />
intervention<br />
3 Breaker with Sepam failure No Availability of Installation not<br />
undervoltage trip<br />
the installation protected until<br />
coil (not fail-safe)<br />
remedial<br />
intervention (1)<br />
Loss of auxiliary Yes Safety of the Installation not<br />
power supply<br />
installation available until<br />
remedial<br />
intervention<br />
(1) It is essential to use the watchdog, see the warning notice opposite.<br />
DE80351<br />
Inhibit closing<br />
Closing<br />
O2<br />
O11<br />
N/O<br />
closing<br />
coil<br />
8<br />
7<br />
L<br />
2<br />
3<br />
O1<br />
Trip<br />
5<br />
4<br />
Example of use with shunt trip coil (diagram 1)<br />
Shunt<br />
trip<br />
coil<br />
Breaker closed Breaker open<br />
4 M 1 M<br />
5 I12 2 I11<br />
Setting the Sepam output parameters:<br />
O1: N/O<br />
O2: N/C<br />
O11: N/O<br />
4/19<br />
4