6<br />

DE52153<br />

DE51683<br />

Installation MES114 modules<br />

6/30<br />

Description<br />

L , M and K : 3 removable, lockable screw-type connectors<br />

L : connectors for 4 relay outputs:<br />

b O11: 1 control relay output<br />

b O12 to O14: 3 annunciation relay outputs<br />

M : connectors for 4 independent logic inputs I11 to I14<br />

K<br />

: connectors for 6 logic inputs:<br />

b I21: 1 independent logic input<br />

b I22 to I26: 5 common point logic inputs.<br />

1 25-pin sub-D connector to connect the module to the base unit.<br />

2 Voltage selector switch for MES114E and MES114F module inputs, to be set to:<br />

b V DC for 10 DC voltage inputs (default setting)<br />

b V AC for 10 AC voltage inputs.<br />

3 Label to be filled in to indicate the chosen parameter setting for MES114E and<br />

MES114F input voltages.<br />

The parameter setting status can be accessed in the "Sepam Diagnosis" screen of<br />

the SFT2841 software tool.<br />

Parameter setting of the inputs for AC voltage (V AC setting) inhibits the "operating<br />

time measurement" function.<br />

Assembly<br />

1. Insert the 2 pins on the MES module into the slots 1 on the base unit.<br />

2. Flatten the module up against the base unit to plug it into the connector 2.<br />

3. Tighten the mounting screw 3.<br />