sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
6<br />
DE52153<br />
DE51683<br />
Installation MES114 modules<br />
6/30<br />
Description<br />
L , M and K : 3 removable, lockable screw-type connectors<br />
L : connectors for 4 relay outputs:<br />
b O11: 1 control relay output<br />
b O12 to O14: 3 annunciation relay outputs<br />
M : connectors for 4 independent logic inputs I11 to I14<br />
K<br />
: connectors for 6 logic inputs:<br />
b I21: 1 independent logic input<br />
b I22 to I26: 5 common point logic inputs.<br />
1 25-pin sub-D connector to connect the module to the base unit.<br />
2 Voltage selector switch for MES114E and MES114F module inputs, to be set to:<br />
b V DC for 10 DC voltage inputs (default setting)<br />
b V AC for 10 AC voltage inputs.<br />
3 Label to be filled in to indicate the chosen parameter setting for MES114E and<br />
MES114F input voltages.<br />
The parameter setting status can be accessed in the "Sepam Diagnosis" screen of<br />
the SFT2841 software tool.<br />
Parameter setting of the inputs for AC voltage (V AC setting) inhibits the "operating<br />
time measurement" function.<br />
Assembly<br />
1. Insert the 2 pins on the MES module into the slots 1 on the base unit.<br />
2. Flatten the module up against the base unit to plug it into the connector 2.<br />
3. Tighten the mounting screw 3.<br />
PCRED301005EN - 06/<strong>20</strong>08