3<br />

Protection functions Remanent undervoltage<br />

ANSI code 27R<br />

3/6<br />

MT10875<br />

Operation<br />

This protection is single-phase:<br />

b it picks up when the U21 phase-to-phase voltage is less than the Us set point<br />

b the protection includes a definite time delay.<br />

Block diagram<br />

U21<br />

(or V1)<br />

Characteristics<br />

Us set point<br />

Setting 5 % Unp to 100 % Unp<br />

Accuracy (1) ±2 % or 0.005 Unp<br />

Resolution 1 %<br />

Drop-out/pick-up ratio 103 % ±2.5 %<br />

Time delay T<br />

Setting 50 ms to 300 s<br />

Accuracy (1) ±2 %, or ±25 ms<br />

Resolution 10 ms or 1 digit<br />

Characteristic times<br />

U < Us<br />

Operation time < 40 ms<br />

Overshoot time < <strong>20</strong> ms<br />

Reset time < 30 ms<br />

(1) In reference conditions (IEC 60255-6).<br />

T<br />

0<br />

time-delayed output<br />

“pick-up” signal<br />

PCRED301005EN - 06/<strong>20</strong>08