2<br />

Network diagnosis<br />

functions<br />

2/10<br />

Disturbance recording<br />

Operation<br />

This function is used to record analog signal and logical states.<br />

Record storage is activated according to parameter setting by a triggering event (see<br />

Control and monitoring functions - Disturbance recording triggering).<br />

The stored event begins before the triggering event and continues afterwards.<br />

The record comprises the following information:<br />

b values sampled from the different signals<br />

b date<br />

b characteristics of the recorded channels.<br />

The files are recorded in FIFO (First In First Out) type shift storage: the oldest record<br />

is erased when a new record is triggered.<br />

Transfer<br />

Files may be transferred locally or remotely:<br />

b locally: using a PC which is connected to the pocket terminal connector and has<br />

the SFT2841 software tool<br />

b remotely: using a software tool specific to the remote monitoring and control<br />

system.<br />

Recovery<br />

The signals are recovered from a record by means of the SFT2826 software tool.<br />

MT10181<br />

Principle<br />

stored record<br />

Characteristics<br />

triggering event<br />

(1)<br />

Record duration x periods before the triggering event (1)<br />

total 86 periods<br />

Record content Set-up file:<br />

date, channel characteristics, measuring transformer ratio<br />

Sample file:<br />

12 values per period/recorded signal<br />

Analog signals recorded (2) 4 current channels (I1, I2, I3, I0) or<br />

4 voltage channels (V1, V2, V3)<br />

Logical signals 10 digital inputs, outputs O1, pick-up<br />

Number of stored records 2<br />

File format COMTRADE 97<br />

(1) According to parameter setting with the SFT2841 (default setting 36 cycles).<br />

(2) According to sensor type and connection.<br />

time<br />

PCRED301005EN - 06/<strong>20</strong>08