Modbus communication Access to remote settings<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Description of settings<br />

Data format<br />

All the settings are transmitted in signed 32-bit whole number form<br />

(encoding, as a complement of 2).<br />

Particular setting value:<br />

7FFF FFFFh means that the setting is outside the validity range.<br />

1 The Enabled or Disabled setting is encoded as follows:<br />

0 = Disabled, 1 = Enabled<br />

2 The tripping curve setting is encoded as follows:<br />

0 = definite<br />

1 = standard inverse time 9 = IEC VIT/<br />

2 = long time inverse 10 = IEC EIT/C<br />

3 = very inverse time 11 = IEEE Mod. inverse<br />

4 = extremely inverse time 12 = IEEE Very inverse<br />

5 = ultra inverse time 13 = IEEE Extr. inverse<br />

6 = RI 14 = IAC inverse<br />

7 = IEC SIT/A 15 = IAC very inverse<br />

8 = IEC LTI/B 16 = IAC extr. inverse<br />

3 The setting of the timer hold curve is encoded as follows:<br />

0 = definite time<br />

1 = IDMT<br />

4 The H2 restraint variable is encoded as follows:<br />

0 = H2 restraint<br />

1 = no H2 restraint<br />

5 The tripping curve setting is:<br />

0 = definite time<br />

1 = IDMT<br />

6 The negative sequence factor is:<br />

0 = None (0)<br />

1 = Low (2.25)<br />

2 = Average (4.5)<br />

3 = High (9)<br />

7 Acknowledgment of the ambient temperature is encoded as follows:<br />

0 = No<br />

1 = Yes<br />

8<br />

9<br />

Not used<br />

The inhibition input setting is encoded as follows:<br />

0 = No inhibition<br />

1 = Inhibit recloser by logic input I26<br />

10 Not used<br />

11<br />

The activation mode of each of the cycles is encoded as follows:<br />

Correspondence between bit position and protection according to the table below:<br />

Bit Activation by<br />

0 Inst O/C 1<br />

1 Time-delayed O/C 1<br />

2 Inst O/C 2<br />

3 Time-delayed O/C 2<br />

4 Inst E/F 1<br />

5 Time-delayed E/F 1<br />

6 Inst E/F 2<br />

7 Time-delayed E/F 2<br />

The bit status is encoded as follows:<br />

0 = No activation by the protection<br />

1 = Activation by the protection.<br />

5/25<br />