sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
4<br />
Control and monitoring<br />
functions<br />
4/12<br />
DE80063<br />
Switching of groups of settings<br />
Description<br />
There are 4 relays for the phase overcurrent and earth fault protection functions, split<br />
into two groups of 2 relays, called group A and group B respectively.<br />
The use of the protection relays is determined by parameter setting.<br />
The switching of groups of settings function enables the group A or group B<br />
protection functions to be activated:<br />
b according to the status of logic input I13<br />
v I13 = 0: activation of group A<br />
v I13 = 1: activation of group B<br />
b or via the communication link<br />
v TC3: activation of group A<br />
v TC4: activation of group B.<br />
The use of the switching of groups of settings functions does not exclude the use of<br />
the logic discrimination function.<br />
Block diagram<br />
Choice via input I13<br />
Input I13<br />
Choice via remote control<br />
Group A (TC3)<br />
Group B (TC4)<br />
Choice via input I13<br />
Input I13<br />
Choice via remote control<br />
Group B (TC4)<br />
Group A (TC3)<br />
TS/TC equivalence for each protocol<br />
Modbus DNP3 IEC 60870-5-103 IEC 61850<br />
TC Binary Output ASDU, FUN, INF LN.DO.DA<br />
1<br />
0<br />
1<br />
0<br />
TC8 BO03 - RDRE1.RcdInh.ctlVal<br />
TC9 BO04 - RDRE1.RcdInh.ctlVal<br />
TC10 BO05 - RDRE1.RcdTrg.ctlVal<br />
&<br />
&<br />
&<br />
&<br />
u 1<br />
Group A<br />
Group B<br />
u 1<br />
PCRED301005EN - 06/<strong>20</strong>08