4<br />

Control and monitoring<br />

functions<br />

4/12<br />

DE80063<br />

Switching of groups of settings<br />

Description<br />

There are 4 relays for the phase overcurrent and earth fault protection functions, split<br />

into two groups of 2 relays, called group A and group B respectively.<br />

The use of the protection relays is determined by parameter setting.<br />

The switching of groups of settings function enables the group A or group B<br />

protection functions to be activated:<br />

b according to the status of logic input I13<br />

v I13 = 0: activation of group A<br />

v I13 = 1: activation of group B<br />

b or via the communication link<br />

v TC3: activation of group A<br />

v TC4: activation of group B.<br />

The use of the switching of groups of settings functions does not exclude the use of<br />

the logic discrimination function.<br />

Block diagram<br />

Choice via input I13<br />

Input I13<br />

Choice via remote control<br />

Group A (TC3)<br />

Group B (TC4)<br />

Choice via input I13<br />

Input I13<br />

Choice via remote control<br />

Group B (TC4)<br />

Group A (TC3)<br />

TS/TC equivalence for each protocol<br />

Modbus DNP3 IEC 60870-5-103 IEC 61850<br />

TC Binary Output ASDU, FUN, INF LN.DO.DA<br />

1<br />

0<br />

1<br />

0<br />

TC8 BO03 - RDRE1.RcdInh.ctlVal<br />

TC9 BO04 - RDRE1.RcdInh.ctlVal<br />

TC10 BO05 - RDRE1.RcdTrg.ctlVal<br />

&<br />

&<br />

&<br />

&<br />

u 1<br />

Group A<br />

Group B<br />

u 1<br />

PCRED301005EN - 06/<strong>20</strong>08