7<br />

Commissioning Checking phase current<br />

input connections<br />

LPCT type current sensors<br />

Description<br />

Check to be performed for Sepam S<strong>20</strong>, S23, T<strong>20</strong>, T23<br />

or M<strong>20</strong>, when phase currents are measured by<br />

LPCT-type current sensors.<br />

Phase current measurement by LPCT<br />

sensors<br />

b The 3 LPCT current sensors are connected via an<br />

RJ45 plug to the CCA670 connector which is to be<br />

mounted on the rear panel of Sepam, identified as<br />

b The connection of only one or two LPCT sensors is<br />

not allowed and causes Sepam to go into the fail-safe<br />

position<br />

b The primary rated current In measured by the LPCT<br />

sensors is to be entered as a Sepam general setting<br />

and configured by microswitches on the CCA670<br />

connector.<br />

7/26<br />

B<br />

DE80136<br />

Procedure<br />

The tests to be carried out to check phase current input connections are the<br />

same whether the phase currents are measured by CTs or by LPCT sensors.<br />

Only the Sepam current input connection procedure and current injection<br />

values change.<br />

To test current inputs connected to LPCT sensors with a standard injection box, the<br />

ACE917 injection adapter is required.<br />

The ACE917 adapter is inserted between:<br />

b The standard injection box<br />

b The LPCT test plug:<br />

v integrated in the Sepam CCA670 connector<br />

v or transferred by means of the CCA613 accessory.<br />

The ACE917 injection adapter should be set according to the currents selected on<br />

the CCA670 connector: the ACE917 setting should be equal to the number of the<br />

microswitch that is set to 1 on the CCA670.<br />

The injection value depends on the primary rated current selected on the CCA670<br />

connector and entered in the Sepam general settings, i.e.:<br />

b 1 A for the following values (in Amps): 25, 50, 100, 133, <strong>20</strong>0, 3<strong>20</strong>, 400, 630<br />

b 5 A for the following values (in Amps): 125, 250, 500, 666, 1000, 1600, <strong>20</strong>00, 3150.<br />

Block diagram (without CCA613 accessory)<br />

Current<br />

generator<br />

Sepam<br />

S<strong>20</strong>/S23/<br />

T<strong>20</strong>/T23/M<strong>20</strong><br />

PCRED301005EN - 06/<strong>20</strong>08