7<br />
Commissioning Checking phase current<br />
input connections<br />
LPCT type current sensors<br />
Description<br />
Check to be performed for Sepam S<strong>20</strong>, S23, T<strong>20</strong>, T23<br />
or M<strong>20</strong>, when phase currents are measured by<br />
LPCT-type current sensors.<br />
Phase current measurement by LPCT<br />
sensors<br />
b The 3 LPCT current sensors are connected via an<br />
RJ45 plug to the CCA670 connector which is to be<br />
mounted on the rear panel of Sepam, identified as<br />
b The connection of only one or two LPCT sensors is<br />
not allowed and causes Sepam to go into the fail-safe<br />
position<br />
b The primary rated current In measured by the LPCT<br />
sensors is to be entered as a Sepam general setting<br />
and configured by microswitches on the CCA670<br />
connector.<br />
7/26<br />
B<br />
DE80136<br />
Procedure<br />
The tests to be carried out to check phase current input connections are the<br />
same whether the phase currents are measured by CTs or by LPCT sensors.<br />
Only the Sepam current input connection procedure and current injection<br />
values change.<br />
To test current inputs connected to LPCT sensors with a standard injection box, the<br />
ACE917 injection adapter is required.<br />
The ACE917 adapter is inserted between:<br />
b The standard injection box<br />
b The LPCT test plug:<br />
v integrated in the Sepam CCA670 connector<br />
v or transferred by means of the CCA613 accessory.<br />
The ACE917 injection adapter should be set according to the currents selected on<br />
the CCA670 connector: the ACE917 setting should be equal to the number of the<br />
microswitch that is set to 1 on the CCA670.<br />
The injection value depends on the primary rated current selected on the CCA670<br />
connector and entered in the Sepam general settings, i.e.:<br />
b 1 A for the following values (in Amps): 25, 50, 100, 133, <strong>20</strong>0, 3<strong>20</strong>, 400, 630<br />
b 5 A for the following values (in Amps): 125, 250, 500, 666, 1000, 1600, <strong>20</strong>00, 3150.<br />
Block diagram (without CCA613 accessory)<br />
Current<br />
generator<br />
Sepam<br />
S<strong>20</strong>/S23/<br />
T<strong>20</strong>/T23/M<strong>20</strong><br />
PCRED301005EN - 06/<strong>20</strong>08