7<br />

Commissioning Checking optional module<br />

connections<br />

7/32<br />

Checking temperature sensor input<br />

connections to the MET148-2 module<br />

The temperature monitoring function provided by Sepam T<strong>20</strong>, T23 or M<strong>20</strong> units<br />

checks the connection of each sensor that is configured.<br />

An "RTD FAULT" alarm is generated whenever one of the sensors is detected as<br />

being short-circuited or disconnected (absent).<br />

To identify the faulty sensor or sensors:<br />

1. Display the temperature values measured by Sepam T<strong>20</strong> or M<strong>20</strong> using the<br />

SFT2841 software.<br />

2. Check the consistency of the temperatures measured:<br />

b The temperature displayed is "****" if the sensor is short-circuited (T < -35°C<br />

or T < -31°F)<br />

b The temperature displayed is "-****" if the sensor is disconnected (T > <strong>20</strong>5°C<br />

or T > 401°F).<br />

Checking the analog output connection to<br />

the MSA141 module<br />

1. Identify the measurement associated by parameter setting with the analog output<br />

using the SFT2841 software.<br />

2. Simulate, if necessary, the measurement linked to the analog output by injection.<br />

3. Check the consistency between the value measured by Sepam and the indication<br />

given by the device connected to the analog output.<br />

PCRED301005EN - 06/<strong>20</strong>08