4<br />

MT10190<br />

MT10191<br />

Control and monitoring<br />

functions<br />

O1<br />

I11<br />

I12<br />

Wiring for shunt trip unit.<br />

O1<br />

I11<br />

I12<br />

4/8<br />

A<br />

M<br />

A<br />

M<br />

5<br />

4<br />

1<br />

2<br />

4<br />

5<br />

5<br />

4<br />

1<br />

2<br />

4<br />

5<br />

D<br />

D<br />

+<br />

_<br />

+<br />

_<br />

DE52238<br />

Circuit breaker / contactor control<br />

Associated functions<br />

Trip circuit supervision and open / closed<br />

matching<br />

Description<br />

This supervision is designed for trip circuits:<br />

b with shunt trip units<br />

The function detects:<br />

v circuit continuity<br />

v loss of supply<br />

v mismatching of position contacts.<br />

The function inhibits closing of the breaking device.<br />

b with undervoltage trip units<br />

The function detects mismatching of position contacts, coil supervision being<br />

unnecessary in this case.<br />

The information is accessible in the matrix and via the remote indication TS43.<br />

Block diagram (1)<br />

Wiring for undervoltage trip unit. (1) With MES option.<br />

The function is activated if inputs I11 and I12 are set respectively as circuit breaker "open<br />

position" and circuit breaker "closed position".<br />

TS/TC equivalence for each protocol<br />

Modbus DNP3 IEC 60870-5-103 IEC 61850<br />

TS Binary Input ASDU, FUN, INF LN.DO.DA<br />

TS43 BI6 (B2X) 1, 160, 36 XCBR1.EEHealth.stVal<br />

BI8 (Others) 1, 160, 36 XCBR1.EEHealth.stVal<br />

Open and close order supervision<br />

Description<br />

Following a circuit breaker open or close order, the system checks whether, after a<br />

<strong>20</strong>0 ms time delay, the circuit breaker has actually changed status.<br />

If the circuit breaker status does not match the last order sent, a "Control fault"<br />

message and remote indication TS45 are generated.<br />

TS/TC equivalence for each protocol<br />

Modbus DNP3 IEC 60870-5-103 IEC 61850<br />

TS Binary Input ASDU, FUN, INF LN.DO.DA<br />

TS45 BI5 (B2X) 1, <strong>20</strong>, 5 Command Termination -<br />

BI7 (Others) 1, <strong>20</strong>, 5 Command Termination -<br />

PCRED301005EN - 06/<strong>20</strong>08