Machine operation<br />
assistance functions<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
Running hours counter and<br />
operating time<br />
Thermal capacity used<br />
Running hours counter / operating time<br />
The counter gives the running total of time during which the protected device (motor<br />
or transformer) has been operating (I > 0.1Ib). The initial counter value may be<br />
modified using the SFT2841 software.<br />
The counter is saved every 4 hours.<br />
Readout<br />
The measurements may be accessed via:<br />
b the display of a Sepam with advanced UMI by pressing the key<br />
b the display of a PC with the SFT2841 software<br />
b the communication link.<br />
Characteristics<br />
Range 0 to 65535<br />
Unit hours<br />
Thermal capacity used<br />
Operation<br />
The thermal capacity used is calculated by the thermal protection function.<br />
The thermal capacity used is related to the load. The thermal capacity used<br />
measurement is given as a percentage of the rated thermal capacity.<br />
Saving of thermal capacity used<br />
When the protection unit trips, the current thermal capacity used increased by 10 % (1)<br />
is saved. The saved value is reset to 0 when the thermal capacity used has<br />
decreased sufficiently for the start inhibit time delay to be zero. The saved value is<br />
used again after a Sepam power outage, making it possible to start over with the<br />
temperature buildup that caused the trip.<br />
(1) The 10 % increase is used to take into account the average temperature buildup of motors<br />
when starting.<br />
Readout<br />
The measurements may be accessed via:<br />
b the display of a Sepam with advanced UMI by pressing the key<br />
b the display of a PC with the SFT2841 software<br />
b the communication link<br />
b an analog converter with the MSA141 option.<br />
Characteristics<br />
Measurement range 0 to 800 %<br />
Unit %<br />
Display format 3 significant digits<br />
Resolution 1 %<br />
Refresh interval 1 second (typical)<br />