Control and monitoring<br />
functions<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
Circuit breaker / contactor control<br />
Associated functions<br />
Latching / acknowledgment<br />
Description<br />
The tripping outputs of all the protection functions and all the logic inputs may be<br />
latched individually.<br />
Logic outputs may not be latched. The logic outputs set up in pulse mode maintain<br />
pulse-type operation, even when linked to latched data.<br />
Latched data are saved in the event of a power failure.<br />
All latched data may be acknowledged locally on the UMI, or remotely by means of<br />
a logic input or via the communication link.<br />
The "Latching / acknowledgment" function associated with the "Circuit breaker /<br />
contactor control" function may be used to perform the ANSI 86 "lockout relay"<br />
function.<br />
TS/TC equivalence for each protocol<br />
Modbus DNP3 IEC 60870-5-103 IEC 61850<br />
TC Binary Output ASDU, FUN, INF LN.DO.DA<br />
TC5 BO2 <strong>20</strong>, 160, 19 LLN0.LEDRs.ctlVal<br />
TC/circuit breaker position discrepancy<br />
Description<br />
This function detects a discrepancy between the last remote control order received<br />
and the actual position of the circuit breaker.<br />
The information is accessible via remote indication TS42.<br />
TS/TC equivalence for each protocol<br />
Modbus DNP3 IEC 60870-5-103 IEC 61850<br />
TS Binary Input ASDU, FUN, INF LN.DO.DA<br />
TS42 BI7 (B2X) - -<br />
BI9 (Others) - -<br />
TC Binary Output ASDU, FUN, INF LN.DO.DA<br />
TC1 BO0 <strong>20</strong>, 21, 1 (OFF) CSWI1.POS.ctlVal<br />
TC2 BO1 <strong>20</strong>, 21, 1 (ON) CSWI1.POS.ctlVal<br />
Tripping<br />
Description<br />
Trip information can be accessed via the remote indication for Sepam check-word, bit<br />
4. It indicates whether a Sepam internal or external protection has tripped.<br />
TS/TC equivalence for each protocol<br />
Modbus DNP3 IEC 60870-5-103 IEC 61850<br />
Binary Input ASDU, FUN, INF LN.DO.DA<br />
Check-<br />
word,<br />
bit 4<br />
BI35 (B2X) 2, 160, 68 PTRC1.Tr<br />
BI61 (Others) 2, 160, 68 PTRC1.Tr<br />
4/7<br />
4