MT10188<br />

MT10189<br />

Control and monitoring<br />

functions<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Circuit breaker / contactor control<br />

Associated functions<br />

Latching / acknowledgment<br />

Description<br />

The tripping outputs of all the protection functions and all the logic inputs may be<br />

latched individually.<br />

Logic outputs may not be latched. The logic outputs set up in pulse mode maintain<br />

pulse-type operation, even when linked to latched data.<br />

Latched data are saved in the event of a power failure.<br />

All latched data may be acknowledged locally on the UMI, or remotely by means of<br />

a logic input or via the communication link.<br />

The "Latching / acknowledgment" function associated with the "Circuit breaker /<br />

contactor control" function may be used to perform the ANSI 86 "lockout relay"<br />

function.<br />

TS/TC equivalence for each protocol<br />

Modbus DNP3 IEC 60870-5-103 IEC 61850<br />

TC Binary Output ASDU, FUN, INF LN.DO.DA<br />

TC5 BO2 <strong>20</strong>, 160, 19 LLN0.LEDRs.ctlVal<br />

TC/circuit breaker position discrepancy<br />

Description<br />

This function detects a discrepancy between the last remote control order received<br />

and the actual position of the circuit breaker.<br />

The information is accessible via remote indication TS42.<br />

TS/TC equivalence for each protocol<br />

Modbus DNP3 IEC 60870-5-103 IEC 61850<br />

TS Binary Input ASDU, FUN, INF LN.DO.DA<br />

TS42 BI7 (B2X) - -<br />

BI9 (Others) - -<br />

TC Binary Output ASDU, FUN, INF LN.DO.DA<br />

TC1 BO0 <strong>20</strong>, 21, 1 (OFF) CSWI1.POS.ctlVal<br />

TC2 BO1 <strong>20</strong>, 21, 1 (ON) CSWI1.POS.ctlVal<br />

Tripping<br />

Description<br />

Trip information can be accessed via the remote indication for Sepam check-word, bit<br />

4. It indicates whether a Sepam internal or external protection has tripped.<br />

TS/TC equivalence for each protocol<br />

Modbus DNP3 IEC 60870-5-103 IEC 61850<br />

Binary Input ASDU, FUN, INF LN.DO.DA<br />

Check-<br />

word,<br />

bit 4<br />

BI35 (B2X) 2, 160, 68 PTRC1.Tr<br />

BI61 (Others) 2, 160, 68 PTRC1.Tr<br />

4/7<br />