2<br />
Metering functions Phase current<br />
Residual current<br />
2/4<br />
Phase current<br />
Operation<br />
This function gives the RMS value of the phase currents:<br />
b I1: phase 1 current<br />
b I2: phase 2 current<br />
b I3: phase 3 current.<br />
It is based on RMS current measurement and takes into account harmonics up to<br />
number 17.<br />
Readout<br />
The measurements may be accessed via:<br />
b the display of a Sepam with advanced UMI by pressing the key<br />
b the display of a PC with the SFT2841 software<br />
b the communication link<br />
b an analog converter with the MSA141 option.<br />
Characteristics<br />
Measurement range 0.1 to 1.5 In (1)<br />
Unit A or kA<br />
Accuracy typically ±1 % (2)<br />
±2 % from 0.3 to 1.5 In<br />
±5 % if < 0.3 In<br />
Display format (3) 3 significant digits<br />
Resolution 0.1 A or 1 digit<br />
Refresh interval 1 second (typical)<br />
(1) In rated current set in the general settings.<br />
(2) At In, in reference conditions (IEC 60255-6).<br />
(3) Display of values: 0.02 to 40 In.<br />
Residual current<br />
Operation<br />
This operation gives the RMS value of the residual current I0.<br />
It is based on measurement of the fundamental component.<br />
Readout<br />
The measurements may be accessed via:<br />
b the display of a Sepam with advanced UMI by pressing the key<br />
b the display of a PC with the SFT2841 software<br />
b the communication link<br />
b an analog converter with the MSA141 option.<br />
Characteristics<br />
Measurement range<br />
Connection to 3 phase CT: 0.1 to 1.5 In0 (1)<br />
Connection to 1 CT 0.1 to 1.5 In0 (1)<br />
Connection to core balance CT with ACE990 0.1 to 1.5 In0 (1)<br />
Connection to CSH residual<br />
current sensor<br />
2 A rating 0.2 to 3 A<br />
<strong>20</strong> A rating 2 to 30 A<br />
Unit<br />
Accuracy<br />
A or kA<br />
(2) typically ±1 % at In0<br />
±2 % from 0.3 to 1.5 In0<br />
±5 % if < 0.3 In0<br />
Display format 3 significant digits<br />
Resolution 0.1 A or 1 digit<br />
(1) In0 rated current set in the general settings.<br />
(2) in reference conditions (IEC 60255-6), excluding sensor accuracy.<br />
PCRED301005EN - 06/<strong>20</strong>08