2<br />

Metering functions Phase current<br />

Residual current<br />

2/4<br />

Phase current<br />

Operation<br />

This function gives the RMS value of the phase currents:<br />

b I1: phase 1 current<br />

b I2: phase 2 current<br />

b I3: phase 3 current.<br />

It is based on RMS current measurement and takes into account harmonics up to<br />

number 17.<br />

Readout<br />

The measurements may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link<br />

b an analog converter with the MSA141 option.<br />

Characteristics<br />

Measurement range 0.1 to 1.5 In (1)<br />

Unit A or kA<br />

Accuracy typically ±1 % (2)<br />

±2 % from 0.3 to 1.5 In<br />

±5 % if < 0.3 In<br />

Display format (3) 3 significant digits<br />

Resolution 0.1 A or 1 digit<br />

Refresh interval 1 second (typical)<br />

(1) In rated current set in the general settings.<br />

(2) At In, in reference conditions (IEC 60255-6).<br />

(3) Display of values: 0.02 to 40 In.<br />

Residual current<br />

Operation<br />

This operation gives the RMS value of the residual current I0.<br />

It is based on measurement of the fundamental component.<br />

Readout<br />

The measurements may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link<br />

b an analog converter with the MSA141 option.<br />

Characteristics<br />

Measurement range<br />

Connection to 3 phase CT: 0.1 to 1.5 In0 (1)<br />

Connection to 1 CT 0.1 to 1.5 In0 (1)<br />

Connection to core balance CT with ACE990 0.1 to 1.5 In0 (1)<br />

Connection to CSH residual<br />

current sensor<br />

2 A rating 0.2 to 3 A<br />

<strong>20</strong> A rating 2 to 30 A<br />

Unit<br />

Accuracy<br />

A or kA<br />

(2) typically ±1 % at In0<br />

±2 % from 0.3 to 1.5 In0<br />

±5 % if < 0.3 In0<br />

Display format 3 significant digits<br />

Resolution 0.1 A or 1 digit<br />

(1) In0 rated current set in the general settings.<br />

(2) in reference conditions (IEC 60255-6), excluding sensor accuracy.<br />

PCRED301005EN - 06/<strong>20</strong>08