PE50586<br />

Modbus communication Configuring the communication<br />

interfaces<br />

SFT2841: Modbus advanced parameters window.<br />

SFT2841: communication configuration window for<br />

ACE969FO.<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Configuring Modbus advanced parameters<br />

The Sepam remote control mode is selected from the Advanced parameters window.<br />

Advanced parameters Authorized values Default value<br />

Remote control mode Direct or SBO (Select<br />

Before Operate) mode<br />

Direct<br />

Configuring the physical layer of the ACE969-2 E-LAN port<br />

The E-LAN port on the ACE969TP-2 and ACE969FO-2 communication interfaces is<br />

a<br />

2-wire RS 485 port.<br />

The configuration parameters for the physical layer of the E-LAN port are:<br />

b Sepam address<br />

b transmission speed<br />

b parity check type.<br />

The number of stop bits is always fixed at 1.<br />

If a configuration with Parity has been selected, each character will contain 11 bits<br />

(1 start bit + 8 data bits + 1parity bit + 1 stop bit)<br />

If a No Parity configuration has been selected, each character will contain 10 bits<br />

(1 start bit + 8 data bits + 1 stop bit).<br />

Parameters Authorized values Default value<br />

Sepam address 1 to 247 1<br />

Speed 4800, 9600, 19<strong>20</strong>0 or<br />

38400 bauds<br />

38400 bauds<br />

Parity None, Even or Odd Odd<br />

Configuration tips<br />

b The Sepam address MUST be assigned before Sepam is connected to the<br />

communication network.<br />

b You are also strongly advised to set the other physical layer configuration<br />

parameters before making the connection to the communication network.<br />

b Modifying the configuration parameters during normal operation will not disturb<br />

Sepam but will reset the communication port.<br />