Protection functions Underfrequency<br />

ANSI code 81L<br />

3/34<br />

MT10543<br />

Operation<br />

The function picks up when the positive sequence voltage frequency is below the set<br />

point and if the positive sequence voltage is more than <strong>20</strong> % of Vnp (Unp/3).<br />

If a single VT is connected (U21), the function picks up when the frequency is below<br />

the set point and the U21 voltage is more than <strong>20</strong> % of Unp.<br />

It includes a definite time delay T.<br />

Block diagram<br />

U32<br />

U21<br />

Vd<br />

Vd > 0.2 Vnp (1)<br />

(1) Or U21 > 0.2 Unp if only one VT.<br />

If there is only one sensor (U21), the voltage signal is connected to terminals 1<br />

and 2 of the connector CCT640, whatever the phase.<br />

Characteristics<br />

&<br />

F < Fs<br />

Fs set point<br />

Setting 45 to 50 Hz or 55 to 60 Hz<br />

Resolution 0.1 Hz<br />

Accuracy (1) ±0.1 Hz<br />

Pick-up / drop-out difference<br />

Time delay T<br />

0.2 Hz ±0.1 Hz<br />

Setting 100 ms to 300 s<br />

Accuracy (1) ±2 % or ±25 ms<br />

Resolution<br />

Characteristic times<br />

10 ms or 1 digit<br />

(1)<br />

Operation time pick-up < 100 ms (typically 80 ms)<br />

Overshoot time < 100 ms<br />

Reset time < 100 ms<br />

(1) In reference conditions (IEC 60255-6) and df/dt < 3 Hz/s.<br />

T<br />

0<br />

time-delayed output<br />

“pick-up” sortie<br />

PCRED301005EN - 06/<strong>20</strong>08