Modbus communication Access to remote settings<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
Protection settings<br />
They are organized according to increasing ANSI codes.<br />
ANSI 27 - Phase-to-phase undervoltage<br />
Function number: 10xx<br />
Relay 1: xx = 01<br />
Relay 2: xx = 02<br />
Setting Data Format/Unit<br />
1 Enabled or disabled<br />
1<br />
2 Us set point % Unp<br />
3 Tripping time delay 10 ms<br />
4 to 8 Reserved<br />
ANSI 27D/47 - Positive sequence undervoltage<br />
Function number: 08xx<br />
Relay 1: xx = 01<br />
Relay 2: xx = 02<br />
Setting Data Format/Unit<br />
1 Enabled or disabled<br />
1<br />
2 Vsd set point % Unp<br />
3 Tripping time delay 10 ms<br />
4 to 8 Reserved<br />
ANSI 27R - Remanent undervoltage<br />
Function number: 0901<br />
Setting Data Format/Unit<br />
1 Enabled or disabled<br />
1<br />
2 Us set point % Unp<br />
3 Tripping time delay 10 ms<br />
4 to 8 Reserved<br />
ANSI 27S - Phase-to-neutral undervoltage<br />
Function number: 1801<br />
Setting Data Format/Unit<br />
1 Enabled or disabled<br />
1<br />
2 Vs set point % Vnp<br />
3 Tripping time delay 10 ms<br />
4 to 8 Reserved<br />
ANSI 37 - Phase undercurrent<br />
Function number: 0501<br />
Setting Data Format/Unit<br />
1 Enabled or disabled<br />
1<br />
2 Is set point % lb<br />
3 Tripping time delay 10 ms<br />
ANSI 38/49T - Temperature monitoring<br />
Function number: 15xx<br />
Relay 1: xx = 01<br />
Relay 2: xx = 02<br />
Relay 3: xx = 03<br />
Relay 4: xx = 04<br />
Relay 5: xx = 05<br />
Relay 6: xx = 06<br />
Relay 7: xx = 07<br />
Relay 8: xx = 08<br />
Setting Data Format/Unit<br />
1 Enabled or disabled<br />
1<br />
2 Alarm set point °C<br />
3 Trip set point °C<br />
4 to 8 Reserved<br />
5/27<br />
5