14.11.2012 Views

sepam 20 user manual - Schneider Electric

sepam 20 user manual - Schneider Electric

sepam 20 user manual - Schneider Electric

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

6<br />

PE80318<br />

DE80293<br />

Installation ACE990 Core balance CT interface<br />

6/26<br />

Function<br />

The ACE990 is used to adapt measurements between an MV core balance CT with<br />

a ratio of 1/n (50 y n y 1500), and the Sepam residual current input.<br />

Characteristics<br />

Weight 0.64 kg (1.41 lb)<br />

Assembly Mounted on symmetrical DIN rail<br />

Amplitude accuracy ±1%<br />

Phase accuracy < 2°<br />

Maximum permissible current <strong>20</strong> kA - 1 s<br />

(on the primary winding of an MV core<br />

balance CT with a ratio of 1/50 that does not<br />

saturate)<br />

ACE990 core balance CT interface. Operating temperature -5°C to +55°C (+23°F to +131°F)<br />

Storage temperature -25°C to +70°C (-13°F to +158°F)<br />

mm<br />

in<br />

1.97<br />

0.78<br />

0.98<br />

3.03 2.83<br />

0.43<br />

1.81<br />

3.9<br />

0.43<br />

Description and dimensions<br />

E<br />

S<br />

ACE990 input terminal block, for connection of the core balance CT.<br />

ACE990 output terminal block, for connection of the Sepam residual current.<br />

PCRED301005EN - 06/<strong>20</strong>08