2<br />

Switchgear diagnosis<br />

functions<br />

2/16<br />

Operating time<br />

Charging time<br />

Operating time<br />

Operation<br />

This function gives the value of the opening operating time of a breaking device (1) and<br />

change of status of the device open position contact connected to the I11 input (2) .<br />

The function is inhibited when the input is set for AC voltage (3) .<br />

The value is saved in the event of a power failure.<br />

Readout<br />

The measurement may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link.<br />

(1) Refer to switchgear documentation for use of this information.<br />

(2) Optional MES module.<br />

(3) Optional MES114E or MES114F modules.<br />

Characteristics<br />

Measurement range <strong>20</strong> to 100<br />

Unit ms<br />

Accuracy typically ±1 ms<br />

Display format 3 significant digits<br />

Charging time<br />

Operation<br />

This function gives the value of the breaking device (1) operating mechanism charging<br />

time, determined according to the device closed position status change contact and<br />

the end of charging contact connected to the Sepam I12 and I24 (2) .<br />

The value is saved in the event of a power failure.<br />

Readout<br />

The measurement may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link.<br />

(1) Refer to switchgear documentation for use of this information.<br />

(2) Optional MES114 or MES114E or MES114F modules.<br />

Characteristics<br />

Measurement range 1 to <strong>20</strong><br />

Unit s<br />

Accuracy ±0.5 sec<br />

Display format 3 significant digits<br />

PCRED301005EN - 06/<strong>20</strong>08