DE80237<br />

Machine operation<br />

assistance functions<br />

or Is<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Starting current and<br />

starting / overload time<br />

Operation<br />

The starting time is defined as follows:<br />

b If the locked rotor/excessive starting time protection (ANSI code 48/51LR) is<br />

active, the starting time is the time separating the moment when one of the 3 phase<br />

currents exceeds Is and the moment when the 3 currents drop back below Is, Is being<br />

the value of the current set point for protection function 48/51LR.<br />

b If the locked rotor/excessive starting time protection (ANSI code 48/51LR) is not<br />

active, the starting time is the time separating the moment when one of the 3 phase<br />

currents exceeds 1.2 Ib and the moment when the 3 currents drop back below 1.2 Ib.<br />

The maximum phase current obtained during this time corresponds to the starting<br />

current.<br />

Both values are saved in the event of a power failure.<br />

Readout<br />

The measurements may be accessed via:<br />

b the display of a Sepam with advanced UMI by pressing the key<br />

b the display of a PC with the SFT2841 software<br />

b the communication link.<br />

Characteristics<br />

Starting / overload time<br />

Measurement range 0 to 300 s<br />

Unit s or ms<br />

Display format 3 significant digits<br />

Resolution 10 ms or 1 digit<br />

Refresh interval<br />

Starting / overload current<br />

1 second (typical)<br />

Measurement range 48/51LR active Is to 24 In (1)<br />

48/51LR inactive 1.2 Ib to 24 In (1)<br />

Unit A or kA<br />

Display format 3 significant digits<br />

Resolution 0.1 A or 1 digit<br />

Refresh interval<br />

(1) Or 65.5 kA.<br />