Modbus communication Access to remote settings<br />

5/24<br />

Reply frame<br />

The reply sent back by the Sepam is the same as the remote reading reply frame. It<br />

fits into a zone containing a maximum of 125 words at the address <strong>20</strong>00h and is<br />

composed of the effective settings of the function following a semantic check:<br />

<strong>20</strong>00h-<strong>20</strong>7Ch<br />

B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01 B00<br />

Function code Relay number<br />

Settings<br />

..............<br />

(special field for each function)<br />

..............<br />

This zone is read by a "read n words" operation (function 3) at the address <strong>20</strong>00h.<br />

The length of the exchange may unclude:<br />

b the first word only (validity test)<br />

b the maximum size of the reply zone (125 words)<br />

b the usable size of the reply zone (determined by the function being addressed).<br />

However, reading must always begin at the first word in the address zone<br />

(any other address triggers an exception reply "incorrect address").<br />

The first word in the reply zone (function code and relay number) has the same<br />

values as those described for the remote reading reply frame.<br />

b xxyy: with:<br />

v function code xx different from 00 and FFh<br />

v relay number yy different from FFh.<br />

The settings are available and validated. The word is a copy of the "request frame".<br />

The zone contents remain valid until the next request is made.<br />

b 0000h: no "request frame" has been formulated yet, as it is the case, in particular,<br />

when the Sepam is switched on.<br />

The other words are not significant.<br />

b FFFFh: the "request frame" has been processed, but the results in the "reply<br />

frame" are not yet available. It is necessary to repeat "reply frame" reading. The other<br />

words are not significant.<br />

b xxFFh: with function code xx different from 00 and FFh. The function for which the<br />

remote reading request has been made is not valid. The function is not included in<br />

that particular Sepam, or access to settings is impossible, both in read and write<br />

mode.<br />

PCRED301005EN - 06/<strong>20</strong>08