DE80292<br />

DE50564<br />

Installation LPCT type current sensors<br />

Test accessories<br />

10.24<br />

Accessory connection principle<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

CAUTION<br />

6.70<br />

HAZARD OF CUTS<br />

Trim the edges of the cut-out plates to remove any<br />

jagged edges.<br />

Failure to follow this instruction can cause<br />

serious injury.<br />

2.75<br />

ACE917 injection adapter<br />

Function<br />

The ACE917 adapter is used to test the protection chain with a standard injection<br />

box, when Sepam is connected to LPCT sensors.<br />

The ACE917 adapter is inserted between:<br />

b The standard injection box<br />

b The LPCT test plug:<br />

v integrated in the Sepam CCA670/CCA671 interface connector<br />

v or transferred by means of the CCA613 accessory.<br />

The following are supplied with the ACE917 injection adapter:<br />

b Power supply cord<br />

b 3-meter (9.8 ft) cord to connect the ACE917 to the LPCT test plug on<br />

CCA670/CCA671 or CCA613.<br />

DE80045<br />

DE80047<br />

Characteristics<br />

Power supply 115/230 V AC<br />

Protection by time-delayed fuse 5 mm x <strong>20</strong> mm (0.2 x 0.79 in ) 0.25 A rating<br />

CCA613 remote test plug<br />

Function<br />

The CCA613 test plug, flush-mounted on the front of the cubicle, is equipped with a<br />

3-meter (9.8 ft) cord to transfer data from the test plug integrated in the CCA670/<br />

CCA671 interface connector on the rear panel of Sepam.<br />

Dimensions<br />

mm<br />

in<br />

Front view with cover lifted. Right side view.<br />

mm<br />

in<br />

Cut-out.<br />

44<br />

1.73<br />

46<br />

1.81<br />

67,5<br />

2.66<br />

69<br />

2.72<br />

DE80117<br />

mm<br />

in<br />

Lug<br />

Wire<br />

13 50<br />

0.51 1.97<br />

80<br />

3.15<br />

67,5<br />

2.66<br />

6/21<br />