sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
sepam 20 user manual - Schneider Electric
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Protection functions Recloser<br />
ANSI code 79<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
Operation<br />
Initialization of the recloser<br />
The recloser is ready to operate if all of the following conditions are met:<br />
b "CB control" function activated and recloser in service<br />
b circuit breaker closed<br />
b inhibition time delay not running<br />
b none of the recloser inhibition conditions is true (see further on).<br />
Recloser cycles<br />
b case of a cleared fault:<br />
v following a reclosing order, if the fault does not appear after the memory time delay<br />
has run out, the recloser reinitializes and a message appears on the display (see<br />
example 1)<br />
b case of a fault that is not cleared:<br />
v following instantaneous or time-delayed tripping by the protection unit, activation<br />
of the isolation time delay associated with the first active cycle.<br />
At the end of the time delay, a closing order is given, which activates the memory time<br />
delay.<br />
If the protection unit detects the fault before the end of the time delay, a tripping order<br />
is given and the following reclosing cycle is activated.<br />
v after all the active cycles have been run, if the fault still persists, a final trip order<br />
is given, a message appears on the display and closing is locked out until<br />
acknowledgment takes place, according to the parameter setting of the protection<br />
function<br />
b closing on a fault.<br />
If the circuit breaker closes on a fault, or if the fault appears before the end of the<br />
lockout time delay, the recloser is inhibited.<br />
Recloser inhibition conditions<br />
The recloser is inhibited according to the following conditions:<br />
b voluntary open or close order<br />
b recloser put out of service<br />
b receipt of a lockout order on the lockout logic input I26<br />
b appearance of a switchgear-related fault, such as trip circuit fault, or unexecture<br />
control order fault<br />
b opening of the circuit breaker by external tripping via inputs I21, I22 or I23.<br />
Characteristics<br />
Reclosing cycles Setting<br />
Number of cycles 1 to 4<br />
Activation of cycle 1 (1) overcurrent 1 inst. / delayed / inactive<br />
overcurrent 2 inst. / delayed / inactive<br />
earth fault 1 inst. / delayed / inactive<br />
earth fault 2 inst. / delayed / inactive<br />
Activation of cycles 2, 3 and 4 (1) overcurrent 1 inst. / delayed / inactive<br />
overcurrent 2 inst. / delayed / inactive<br />
earth fault 1 inst. / delayed / inactive<br />
Time delays<br />
earth fault 2 inst. / delayed / inactive<br />
Memory time delay 0.05 to 300 s<br />
Isolation time delay cycle 1 0.05 to 300 s<br />
cycle 2 0.05 to 300 s<br />
cycle 3 0.05 to 300 s<br />
cycle 4 0.05 to 300 s<br />
Lockout time delay 0.05 to 300 s<br />
Accuracy ±2 % or 25 ms<br />
Resolution 10 ms or 1 digit<br />
(1) If a protection function that is inactive in relation to the recloser leads to circuit breaker<br />
opening, the recloser is inhibited.<br />
3/31<br />
3