14.11.2012 Views

sepam 20 user manual - Schneider Electric

sepam 20 user manual - Schneider Electric

sepam 20 user manual - Schneider Electric

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Protection functions Recloser<br />

ANSI code 79<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Operation<br />

Initialization of the recloser<br />

The recloser is ready to operate if all of the following conditions are met:<br />

b "CB control" function activated and recloser in service<br />

b circuit breaker closed<br />

b inhibition time delay not running<br />

b none of the recloser inhibition conditions is true (see further on).<br />

Recloser cycles<br />

b case of a cleared fault:<br />

v following a reclosing order, if the fault does not appear after the memory time delay<br />

has run out, the recloser reinitializes and a message appears on the display (see<br />

example 1)<br />

b case of a fault that is not cleared:<br />

v following instantaneous or time-delayed tripping by the protection unit, activation<br />

of the isolation time delay associated with the first active cycle.<br />

At the end of the time delay, a closing order is given, which activates the memory time<br />

delay.<br />

If the protection unit detects the fault before the end of the time delay, a tripping order<br />

is given and the following reclosing cycle is activated.<br />

v after all the active cycles have been run, if the fault still persists, a final trip order<br />

is given, a message appears on the display and closing is locked out until<br />

acknowledgment takes place, according to the parameter setting of the protection<br />

function<br />

b closing on a fault.<br />

If the circuit breaker closes on a fault, or if the fault appears before the end of the<br />

lockout time delay, the recloser is inhibited.<br />

Recloser inhibition conditions<br />

The recloser is inhibited according to the following conditions:<br />

b voluntary open or close order<br />

b recloser put out of service<br />

b receipt of a lockout order on the lockout logic input I26<br />

b appearance of a switchgear-related fault, such as trip circuit fault, or unexecture<br />

control order fault<br />

b opening of the circuit breaker by external tripping via inputs I21, I22 or I23.<br />

Characteristics<br />

Reclosing cycles Setting<br />

Number of cycles 1 to 4<br />

Activation of cycle 1 (1) overcurrent 1 inst. / delayed / inactive<br />

overcurrent 2 inst. / delayed / inactive<br />

earth fault 1 inst. / delayed / inactive<br />

earth fault 2 inst. / delayed / inactive<br />

Activation of cycles 2, 3 and 4 (1) overcurrent 1 inst. / delayed / inactive<br />

overcurrent 2 inst. / delayed / inactive<br />

earth fault 1 inst. / delayed / inactive<br />

Time delays<br />

earth fault 2 inst. / delayed / inactive<br />

Memory time delay 0.05 to 300 s<br />

Isolation time delay cycle 1 0.05 to 300 s<br />

cycle 2 0.05 to 300 s<br />

cycle 3 0.05 to 300 s<br />

cycle 4 0.05 to 300 s<br />

Lockout time delay 0.05 to 300 s<br />

Accuracy ±2 % or 25 ms<br />

Resolution 10 ms or 1 digit<br />

(1) If a protection function that is inactive in relation to the recloser leads to circuit breaker<br />

opening, the recloser is inhibited.<br />

3/31<br />

3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!