Installation CSH30 interposing ring CT<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

turns<br />

turns<br />

turns<br />

turns<br />

PE50033<br />

Connection<br />

The CSH30 is adapted for the type of current transformer, 1 A or 5 A, by<br />

the number of turns of the secondary wiring through the CSH30 interposing ring CT:<br />

b 5 A rating - 4 turns<br />

b 1 A rating - 2 turns<br />

Connection to 5 A secondary circuit Connection to 1 A secondary circuit<br />

1. Plug into the connector.<br />

2. Insert the transformer secondary wire<br />

through the CSH30 interposing ring CT<br />

4times.<br />

PE50034<br />

1. Plug into the connector.<br />

2. Insert the transformer secondary wire<br />

through the CSH30 interposing ring CT<br />

twice.<br />

Connection to Sepam series <strong>20</strong> and Sepam series 40<br />

To residual current I0 input, on connector A , terminals 19 and 18 (shielding).<br />

Connection to Sepam series 80<br />

b To residual current I0 input, on connector E , terminals 15 and 14 (shielding)<br />

b To residual current I'0 input, on connector E , terminals 18 and 17 (shielding).<br />

Recommended cable<br />

b Sheathed cable, shielded by tinned copper braid<br />

b Minimum cable cross-section 0.93 mm² (AWG 18) (max. 2.5 mm², AWG 12)<br />

b Resistance per unit length < 100 mΩ/m (30.5 mΩ/ft)<br />

b Minimum dielectric strength: 1000 V (700 Vrms)<br />

b Maximum length: 2 m (6.6 ft).<br />

It is essential for the CSH30 interposing ring CT to be installed near Sepam<br />

(Sepam - CSH30 link less than 2 m (6.6 ft) long).<br />

Flatten the connection cable against the metal frames of the cubicle.<br />

The connection cable shielding is grounded in Sepam. Do not ground the cable by<br />

any other means.<br />