Use SFT2841 setting and operating<br />
software<br />
Configuration of a Sepam network<br />
Configuration window for the serial link communication<br />
network.<br />
Configuration window for the Ethernet TCP/IP communication<br />
network.<br />
7/8<br />
Direct serial link<br />
The Sepam units are connected to an RS 485 (or fiber-optic) multidrop network.<br />
Depending on the serial link interfaces available on the PC, the PC itself will be<br />
connected either directly to the RS 485 network (or fiber-optic HUB), or via an<br />
RS 232/RS 485 converter (or fiber-optic converter).<br />
The communication parameters to be defined are:<br />
b port: communication port used on the PC<br />
b speed: 4800, 9600, 19<strong>20</strong>0 or 38400 bauds<br />
b parity: None, Even or Odd<br />
b handshake: none, RTS or RTS-CTS<br />
b time-out: from 100 to 3000 ms<br />
b number of retries: from 1 to 3.<br />
Link via Ethernet TCP/IP<br />
The Sepam units are connected to an RS 485 multidrop network over one or more<br />
Ethernet Modbus TCP/IP gateways (for example: EGX gateways or ECI850 servers<br />
that act as the Modbus TCP/IP gateway for the link with the SFT2841).<br />
Use on an IEC 61850 network<br />
SFT2841 can be used on an IEC 61850 network. In this case, it can be used to define<br />
the IEC 61850 configuration of Sepams connected to this network. See the Sepam<br />
IEC 61850 Communication <strong>user</strong>'s <strong>manual</strong> (reference SEPED306024EN) for more<br />
information.<br />
Configuration of the Modbus TCP/IP gateway<br />
See the setup <strong>manual</strong> for the gateway used.<br />
In general, the gateway should be assigned an IP address.<br />
The configuration parameters for the gateway’s RS 485 interface must be defined in<br />
accordance with the Sepam communication interface configuration:<br />
b speed: 4800, 9600, 19<strong>20</strong>0 or 38400 bauds<br />
b character format: 8 data bits + 1 stop bit + parity (none, even, odd).<br />
Configuration of communication on SFT2841<br />
When configuring a Sepam network on SFT2841, the following communication<br />
parameters must be defined:<br />
b Type of device: Modbus gateway, ECI850 or Sepam<br />
b IP address: IP address for the connected remote equipment<br />
b time-out: from 100 to 3000 ms.<br />
A time-out of between 800 ms and 1000 ms is sufficient in most installations.<br />
Communication via the TCP/IP gateway may, however, be slowed down if other<br />
applications want Modbus TCP/IP or IEC 61850 access at the same time.<br />
The time-out value should then be increased (2 to 3 seconds).<br />
b number of retries: from 1 to 3.<br />
Note 1: SFT2841 uses the Modbus TCP/IP communication protocol.<br />
Although communication is IP-based, use of SFT2841 is restricted to a local installation network<br />
based on an Ethernet network (LAN – Local Area Network).<br />
The operation of SFT2841 over a WAN (Wide Area Network) cannot be guaranteed because of<br />
the presence of some routers or firewalls that may reject the Modbus protocol, causing<br />
communication times that would be incompatible with Sepam.<br />
Note 2: SFT2841 allows Sepam protection settings to be modified, and direct activation of the<br />
outputs. These operations, which could involve the operation of electrical equipment (opening<br />
and closing), and thus put the safety of people and installations at risk, are protected by the<br />
Sepam password. In addition to this protection, the E-LANs and S-LANs must be designed as<br />
private networks, protected from external actions by all suitable methods.<br />