14.11.2012 Views

sepam 20 user manual - Schneider Electric

sepam 20 user manual - Schneider Electric

sepam 20 user manual - Schneider Electric

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

PE50031<br />

DE51674<br />

Installation LPCT type current sensors<br />

CLP1 LPCT sensor<br />

CAUTION<br />

HAZARD OF NON-OPERATION<br />

b Set the microswitches for the CCA670/<br />

CCA671 connector before commissioning the<br />

device.<br />

b Check that only one microswitch is in position 1<br />

for each block L1, L2, L3 and that no microswitch<br />

is in the center position.<br />

b Check that the microswitch settings on all 3<br />

blocks are identical.<br />

Failure to follow these instructions can cause<br />

incorrect operation.<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

Function<br />

Low Power Current Transducer (LPCT) type sensors are voltage-output sensors,<br />

which are compliant with the IEC 60044-8 standard.<br />

The <strong>Schneider</strong> <strong>Electric</strong> range of LPCTs includes the following sensors: CLP1, CLP2,<br />

CLP3, TLP160 and TLP190.<br />

CCA670/CCA671<br />

connector<br />

Function<br />

The 3 LPCT sensors are connected to the CCA670 or CCA671 connector on the rear<br />

panel of Sepam.<br />

The connection of only one or two LPCT sensors is not allowed and<br />

causes Sepam to go into fail-safe position.<br />

The two CCA670 and CCA671 interface connectors serve the same purpose,<br />

the difference being the position of the LPCT sensor plugs:<br />

b CCA670: lateral plugs, for Sepam series <strong>20</strong> and Sepam series 40<br />

b CCA671: radial plugs, for Sepam series 80.<br />

Description<br />

1 3 RJ45 plugs to connect the LPCT sensors.<br />

2 3 blocks of microswitches to set the CCA670/CCA671 to the rated phase current<br />

value.<br />

3 Microswitch setting/selected rated current equivalency table (2 In values per<br />

position).<br />

4 9-pin sub-D connector to connect test equipment (ACE917 for direct connector or<br />

via CCA613).<br />

Rating of CCA670/CCA671 connectors<br />

The CCA670/CCA671 connector must be rated according to the rated primary<br />

current In measured by the LPCT sensors. In is the current value that corresponds<br />

to the rated secondary current of 22.5 mV. The possible settings for In are (in A): 25,<br />

50, 100, 125, 133, <strong>20</strong>0, 250, 3<strong>20</strong>, 400, 500, 630, 666, 1000, 1600, <strong>20</strong>00, 3150.<br />

The selected In value should be:<br />

b entered as a Sepam general setting<br />

b configured by microswitch on the CCA670/CCA671 connector.<br />

Operating mode:<br />

1. Use a screwdriver to remove the shield located in the "LPCT settings" zone; the<br />

shield protects 3 blocks of 8 microswitches marked L1, L2, L3.<br />

2. On the L1 block, set the microswitch for the selected rated current to "1" (2 In<br />

values per microswitch).<br />

b The table of equivalencies between the microswitch settings and the selected<br />

rated current In is printed on the connector<br />

b Leave the 7 other microswitches set to "0".<br />

3. Set the other 2 blocks of switches L2 and L3 to the same position as the L1 block<br />

and close the shield.<br />

6/19<br />

6

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!