DE51156<br />

Control and monitoring<br />

functions<br />

4/2<br />

Description<br />

Sepam performs the control and monitoring functions required for electrical network<br />

operation.<br />

Predefined functions<br />

The main control and monitoring functions are predefined and fit the most frequent<br />

cases of use. They are ready to use and are implemented by simple parameter<br />

setting after the necessary logic inputs / outputs are assigned.<br />

The predefined control and monitoring functions can be adapted for particular needs<br />

by customization of the control matrix using the SFT2841 software.<br />

Control matrix<br />

The control matrix is a simple way to assign data from:<br />

b protection functions<br />

b predefined control and monitoring functions<br />

b logic inputs<br />

to the following output data:<br />

b output relays<br />

b 9 LEDs on the front panel of Sepam<br />

b triggering of disturbance recording.<br />

Operating principle<br />

The processing of each control and monitoring function may be broken down into 3<br />

phases:<br />

b acquisition of input data:<br />

v results of protection function processing<br />

v external logic data, connected to the logic inputs of an optional MES114 input /<br />

output module<br />

v remote control orders (TC) received via the communication link<br />

b actual processing of the control and monitoring function<br />

b utilization of the processing results:<br />

v activation of output relays to control an actuator<br />

v information sent to the facility manager:<br />

- by message and/or LED on the Sepam display and SFT2841 software<br />

- by remote indication (TS) via the communication link.<br />

Logic inputs and outputs<br />

The number of Sepam inputs / outputs must be adapted to fit the control and<br />

monitoring functions used.<br />

The 4 outputs included in the Sepam series <strong>20</strong> base unit may be extended by adding<br />

one MES114 modules with 10 logic inputs and 4 output relays.<br />

After selecting the MES114 type required by an application, the logic inputs must be<br />

assigned to functions.<br />