Commissioning Checking the residual current<br />

input connection<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

DE80137<br />

Description<br />

Check to be carried out for Sepam S<strong>20</strong>, S23, T<strong>20</strong>, T23 or M<strong>20</strong>, when the residual<br />

current is measured by a specific sensor:<br />

b CSH1<strong>20</strong> or CSH<strong>20</strong>0 core balance CT<br />

b Another core balance CT connected to an ACE990 interface<br />

b A single 1 A or 5 A CT encompassing the 3 phases.<br />

Procedure<br />

1. Connect the single-phase current generator to inject current into the primary circuit<br />

of the core balance CT or the CT, in accordance with the diagram below:<br />

L1<br />

L2<br />

L3<br />

A<br />

Current generator<br />

I<br />

N<br />

test terminal<br />

box<br />

A<br />

2. Turn on the generator.<br />

3. Inject a 5 A primary residual current.<br />

4. Use the SFT2841 software to check that the residual current value is<br />

approximately equal to 5 A.<br />

5. Turn off the generator.<br />

4<br />

1<br />

5<br />

2<br />

6<br />

3<br />

18<br />

19<br />

B<br />

A<br />

Sepam<br />

S<strong>20</strong>/S23/T<strong>20</strong>/T23/M<strong>20</strong><br />

7/27<br />

7