Protection functions Rate of change of frequency<br />

ANSI code 81R<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

MT10877<br />

Operation<br />

This function picks up when the rate of change of frequency (ROCOF) of the positive<br />

sequence voltage overshoots the set point.<br />

If only one VT is connected (U21), the function is inhibited.<br />

It includes a definite time delay T.<br />

Block diagram<br />

Vd<br />

f<br />

> 0.5 Vn<br />

< Fmax<br />

> Fmin<br />

Characteristics<br />

& dF/dt<br />

> + dFs/dt<br />

< - dFs/dt<br />

dFs/dt set point<br />

Setting 0.1 to 10 Hz/s<br />

Resolution 0.1 Hz/s<br />

Accuracy tripping ±5 % or ±0.1 Hz/s<br />

Time delay T<br />

no tripping ±3 % or ±0.05 Hz/s<br />

Setting 100 ms to 300 s<br />

Accuracy ±2 % or ±25 ms<br />

Resolution 10 ms or 1 digit<br />

Characteristic times (1)<br />

Operation time pick-up < 170 ms (130 ms typical)<br />

Overshoot time < 100 ms<br />

Reset time<br />

(1) In reference conditions (IEC 60255-6).<br />

< 100 ms<br />

1<br />

T<br />

0<br />

time delayed<br />

output<br />

signal “pick-up”<br />

3/35<br />