Modbus communication Access to remote settings<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

CAUTION<br />

RISK OF UNINTENDED OPERATION<br />

b The device must only be configured and set by<br />

qualified personnel, using the results of the<br />

installation protection system study.<br />

b During commissioning of the installation and<br />

following any modification, check that the Sepam<br />

configuration and protection function settings are<br />

consistent with the results of this study.<br />

Failure to follow these instructions can result<br />

in equipment damage.<br />

Remote setting<br />

Data that can be remotely set<br />

Writing of the settings of all the protection functions may be accessed remotely.<br />

Exchange principle<br />

Remote setting is allowed for Sepam units.<br />

Remote setting is carried out for a given function, relay by relay.<br />

It takes place in two steps:<br />

b first of all, the master indicates the function code and relay number, followed by the<br />

values of all the settings in the a "write request frame". The request is acknowledged<br />

to free the network<br />

b the master then reads a reply zone to find the required information by means of a<br />

"reply frame", a reply zone designed for checking that the settings have been<br />

processed. Each function has its own particular reply zone contents. The contents<br />

are same as those of the reply frame.<br />

To use remote setting, it is necessary to make all the settings for the function<br />

concerned, even if some of them have not changed.<br />

Request frame<br />

The request is made by the master using a "write n words" (function 16) operation at<br />

the address 2100h. The zone to be written contains a maximum of 125 words.<br />

It contains the values of all the settings. It consists of the following:<br />

2100h<br />

B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01 B00<br />

Function code Relay number<br />

Settings<br />

..............<br />

(special field for each function)<br />

..............<br />

The content of the address 2100h may be read using a "read n words" (function 3).<br />

The function code field may have the following values:<br />

b 01h to 99h (BCD encoding) for the list of protection functions F01 to F99.<br />

The relay number field is used as follows:<br />

b for protection, it indicates the relay involved, varying from 1 to N, N being the<br />

maximum number of relays available in the Sepam. It may never be equal to 0.<br />

Exception reply<br />

In addition to the usual cases, Sepam can send type 07 exception replies<br />

(not acknowledged) if:<br />

b another remote reading or setting request is being processed<br />

b the remote setting function is inhibited.<br />