Modbus communication Access to remote settings<br />
PCRED301005EN - 06/<strong>20</strong>08<br />
CAUTION<br />
RISK OF UNINTENDED OPERATION<br />
b The device must only be configured and set by<br />
qualified personnel, using the results of the<br />
installation protection system study.<br />
b During commissioning of the installation and<br />
following any modification, check that the Sepam<br />
configuration and protection function settings are<br />
consistent with the results of this study.<br />
Failure to follow these instructions can result<br />
in equipment damage.<br />
Remote setting<br />
Data that can be remotely set<br />
Writing of the settings of all the protection functions may be accessed remotely.<br />
Exchange principle<br />
Remote setting is allowed for Sepam units.<br />
Remote setting is carried out for a given function, relay by relay.<br />
It takes place in two steps:<br />
b first of all, the master indicates the function code and relay number, followed by the<br />
values of all the settings in the a "write request frame". The request is acknowledged<br />
to free the network<br />
b the master then reads a reply zone to find the required information by means of a<br />
"reply frame", a reply zone designed for checking that the settings have been<br />
processed. Each function has its own particular reply zone contents. The contents<br />
are same as those of the reply frame.<br />
To use remote setting, it is necessary to make all the settings for the function<br />
concerned, even if some of them have not changed.<br />
Request frame<br />
The request is made by the master using a "write n words" (function 16) operation at<br />
the address 2100h. The zone to be written contains a maximum of 125 words.<br />
It contains the values of all the settings. It consists of the following:<br />
2100h<br />
B15 B14 B13 B12 B11 B10 B09 B08 B07 B06 B05 B04 B03 B02 B01 B00<br />
Function code Relay number<br />
Settings<br />
..............<br />
(special field for each function)<br />
..............<br />
The content of the address 2100h may be read using a "read n words" (function 3).<br />
The function code field may have the following values:<br />
b 01h to 99h (BCD encoding) for the list of protection functions F01 to F99.<br />
The relay number field is used as follows:<br />
b for protection, it indicates the relay involved, varying from 1 to N, N being the<br />
maximum number of relays available in the Sepam. It may never be equal to 0.<br />
Exception reply<br />
In addition to the usual cases, Sepam can send type 07 exception replies<br />
(not acknowledged) if:<br />
b another remote reading or setting request is being processed<br />
b the remote setting function is inhibited.<br />