Metering functions Phase-to-phase voltage<br />
Phase-to-neutral voltage<br />
2/6<br />
Phase-to-phase voltage<br />
Operation<br />
This function gives the RMS value of the 50 or 60 Hz component of phase-to-phase<br />
voltages (according to voltage sensor connections):<br />
b U21: voltage between phases 2 and 1<br />
b U32: voltage between phases 3 and 2<br />
b U13: voltage between phases 1 and 3.<br />
It is based on measurement of the fundamental component.<br />
Readout<br />
The measurements may be accessed via:<br />
b the display of a Sepam with advanced UMI by pressing the key<br />
b the display of a PC with the SFT2841 software<br />
b the communication link<br />
b an analog converter with the MSA141 option.<br />
Characteristics<br />
Measurement range 0.05 to 1.2 Unp (1)<br />
Unit V or kV<br />
Accuracy (2) ±1 % from 0.5 to 1.2 Unp<br />
±2 % from 0,05 to 0.5 Unp<br />
Display format 3 significant digits<br />
Resolution 1 V or 1 digit<br />
Refresh interval 1 second (typical)<br />
(1) Un nominal rating set in the general settings.<br />
(2) at Un, in reference conditions (IEC 60255-6).<br />
Phase-to-neutral voltage<br />
Operation<br />
This function gives the RMS value of the 50 or 60 Hz component of phase-to-neutral<br />
voltages:<br />
b V1: phase 1 phase-to-neutral voltage<br />
b V2: phase 2 phase-to-neutral voltage<br />
b V3: phase 3 phase-to-neutral voltage.<br />
It is based on measurement of the fundamental component.<br />
Readout<br />
The measurements may be accessed via:<br />
b the display of a Sepam with advanced UMI by pressing the key<br />
b the display of a PC with the SFT2841 software<br />
b the communication link<br />
b an analog converter with the MSA141 option.<br />
Characteristics<br />
Measurement range 0.05 to 1.2 Vnp (1)<br />
Unit V or kV<br />
Accuracy (2) ±1 % from 0.5 to 1.2 Vnp<br />
±2 % from 0.05 to 0.5 Vnp<br />
Display format 3 significant digits<br />
Resolution 1 V or 1 digit<br />
Refresh interval 1 second (typical)<br />
(1) Vnp: primary rated phase-to-neutral voltage (Vnp = Unp/3).<br />
(2) at Vnp in reference conditions (IEC 60255-6).<br />
PCRED301005EN - 06/<strong>20</strong>08