Protection functions Phase-to-neutral undervoltage<br />

ANSI code 27S<br />

PCRED301005EN - 06/<strong>20</strong>08<br />

MT10874<br />

Operation<br />

This protection is three-phase:<br />

b it picks up when one of the 3 phase-to-neutral voltages drops below the Vs set<br />

point<br />

b it has 3 independent outputs available for the control matrix<br />

b it is operational if the number of VTs connected is V1, V2, V3 or U21, U32 with<br />

measurement of V0.<br />

Block diagram<br />

V1<br />

V2<br />

V3<br />

V1 < Vs<br />

V2 < Vs<br />

V3 < Vs<br />

Characteristics<br />

Vs set point<br />

Setting 5 % Vnp to 100 % Vnp<br />

Accuracy (1) ±2 % or 0.005 Vnp<br />

Resolution 1 %<br />

Drop-out/pick-up ratio<br />

Time delay T<br />

103 % ±2.5 %<br />

Setting 50 ms to 300 s<br />

Accuracy (1) ±2 %, or ±25 ms<br />

Resolution<br />

Characteristic times<br />

10 ms or 1 digit<br />

Operation time pick-up < 35 ms (typically 25 ms)<br />

Overshoot time < 35 ms<br />

Reset time<br />

(1) In reference conditions (IEC 60255-6).<br />

< 40 ms<br />

T<br />

T<br />

T<br />

1<br />

0<br />

0<br />

0<br />

time-delayed output<br />

time-delayed output<br />

time-delayed output<br />

“pick-up” signal<br />

3/7<br />