Commissioning Testing and metering equipment<br />
required<br />
7/22<br />
Generators<br />
b Sinusoidal AC current generator:<br />
v 50 or 60 Hz frequency (according to the country)<br />
v single-phase type, adjustable from 0 to 50 Arms<br />
v with connector suited to the built-in test terminal box in the current input connection<br />
diagram<br />
b Sinusoidal AC voltage generator:<br />
v 50 or 60 Hz frequency (according to the country)<br />
v single-phase type, adjustable from 0 to 150 Vrms<br />
v with connector suited to the built-in test terminal box in the voltage input<br />
connection diagram<br />
b DC voltage generator:<br />
v adjustable from 48 to 250 V DC<br />
v for adaptation to the voltage level of the input being tested<br />
v with electric cord and clamps, wire grip or touch probes.<br />
Metering devices<br />
b 1 ammeter, 0 to 50 Arms<br />
b 1 voltmeter, 0 to 150 Vrms.<br />
Computer equipment<br />
b PC with minimum configuration:<br />
v Microsoft Windows XP or Vista<br />
v 400 MHz Pentium processor<br />
v 64 MB of RAM<br />
v <strong>20</strong>0 MB free on hard disk<br />
v CD-ROM drive<br />
b SFT2841 software<br />
b CCA783 serial connection cord between the PC and Sepam.<br />
Documents<br />
b Complete connection diagram of Sepam and additional modules, with:<br />
v phase current input connection to the corresponding CTs via the test terminal box<br />
v residual current input connection<br />
v phase voltage input connection to the corresponding VTs via the test terminal box<br />
v residual voltage input connection to the corresponding VTs via the test terminal<br />
box<br />
v logic input and output connection<br />
v temperature sensor connection<br />
v analog output connection<br />
b Hardware BOMs and installation rules<br />
b All Sepam parameter and protection settings, available in paper format.<br />
PCRED301005EN - 06/<strong>20</strong>08