7<br />

Commissioning Testing and metering equipment<br />

required<br />

7/22<br />

Generators<br />

b Sinusoidal AC current generator:<br />

v 50 or 60 Hz frequency (according to the country)<br />

v single-phase type, adjustable from 0 to 50 Arms<br />

v with connector suited to the built-in test terminal box in the current input connection<br />

diagram<br />

b Sinusoidal AC voltage generator:<br />

v 50 or 60 Hz frequency (according to the country)<br />

v single-phase type, adjustable from 0 to 150 Vrms<br />

v with connector suited to the built-in test terminal box in the voltage input<br />

connection diagram<br />

b DC voltage generator:<br />

v adjustable from 48 to 250 V DC<br />

v for adaptation to the voltage level of the input being tested<br />

v with electric cord and clamps, wire grip or touch probes.<br />

Metering devices<br />

b 1 ammeter, 0 to 50 Arms<br />

b 1 voltmeter, 0 to 150 Vrms.<br />

Computer equipment<br />

b PC with minimum configuration:<br />

v Microsoft Windows XP or Vista<br />

v 400 MHz Pentium processor<br />

v 64 MB of RAM<br />

v <strong>20</strong>0 MB free on hard disk<br />

v CD-ROM drive<br />

b SFT2841 software<br />

b CCA783 serial connection cord between the PC and Sepam.<br />

Documents<br />

b Complete connection diagram of Sepam and additional modules, with:<br />

v phase current input connection to the corresponding CTs via the test terminal box<br />

v residual current input connection<br />

v phase voltage input connection to the corresponding VTs via the test terminal box<br />

v residual voltage input connection to the corresponding VTs via the test terminal<br />

box<br />

v logic input and output connection<br />

v temperature sensor connection<br />

v analog output connection<br />

b Hardware BOMs and installation rules<br />

b All Sepam parameter and protection settings, available in paper format.<br />

PCRED301005EN - 06/<strong>20</strong>08