<strong>DS7200V2</strong>-<strong>EXP</strong> | Installation Guide | 2. System Installation and Setup EN | 192.3.5 No EOL Zone ConfigurationSee Figure 18 when wiring a zone with no EOLresistors.Figure 18: Single Zone Sensor Loop Wiring(No EOL)12345762.3.6 Four-Wire Smoke Detector ConfigurationA four-wire smoke detector can be connected to any ofthe control panel’s on-board sensor loops (L-1 to L-8).A four-wire smoke detector must use a relay module tointerrupt power to the detector in order for the detectorto reset.Configure the output controlling the relay as OutputFunction 1|13 “Fire Verification” (see Output Parameterson page 85 for more information).Make loop connections to L-X (where X = Loop #)and COM terminals. See Figure 19, and Figure 20 onpage 20.Figure 19: 4-wire Smoke Detector (Tamperwired)1- Sensor loop terminal2- Common3- Sensor loop terminal4- Common5- 100 Ω maximum6- Normally Open contacts7- Normally Closed contactsBATT+BATT-ALRM+PO1 SELECTPO1 SMKA B + L-1 COM1654231- Remove jumper plug from PO 1 SELECTjumper2- 2.2 kΩ alarm resistor3- 2.2 kΩ EOL resistor4- Smoke detector5- AUX (+)6- AUX (-)Bosch Security Systems, Inc. | 2/09 | 4998153893-03