12.07.2015 Views

DS7200V2-EXP - Simon Technologies

DS7200V2-EXP - Simon Technologies

DS7200V2-EXP - Simon Technologies

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DS7200V2</strong>-<strong>EXP</strong> | Installation Guide | 2. System Installation and Setup EN | 24If you need to power the DX2010 with an external 12VDC power supply, wire it as shown in Figure 30.Figure 30: DX2010 to Control Panel Wiring(External Power Supply)12372.6.4 DX2010 Auxiliary Output WiringThe DX2010 can provide 12 VDC at up to 100 mAfrom the Auxiliary Output (-) OUT (+) terminals topower external devices such as motion detectors. SeeFigure 31.Figure 31: DX2010 Auxiliary Output Wiring1+OUT- TMPR R B G Y 1 COM56(+) (-)4+OUT-TMPR R B G Y 1 COM1- DX2010 Module2- Green (G) data wire3- Yellow (Y) data wire4- Black (-) wire5- Red (+) wire6- External 12 VDC power source7- Control panel boardBATT+BATT-Do not tie the black (-) output to earthground when using an external powersupply. A ground fault condition is reportedif black (-) is grounded.3241- DX2010 Module2- Motion detectors, photo beams, etc.3- Black (-) wire4- Red (+) wireThe following maximum wire lengths applywhen wiring the DX2010’s auxiliary outputto remotely powered devices, such asPIR’s and smoke detectors:−−15 m (49.2 ft) for 0.8 mm (#22 AWG)wire.30 m (98.4 ft) for 1.2 mm (#18 AWG)wire.Bosch Security Systems, Inc. | 2/09 | 4998153893-03