<strong>DS7200V2</strong>-<strong>EXP</strong> | Installation Guide | 3. Control Panel Programming EN | 99RF Receiver Supervision Interval• Address: 1250• Default: 5 (24 h)• Selections:- 0 = No Supervision- 1 = 1 h- 2 = 2 h- 3 = 4 h- 4 = 12 h- 5 = 24 hRF transmitters (sensors) send a supervisory signal approximately once every 13 min. The RF receiver expects tohear this signal from every transmitter in the interval determined in this parameter. A “Missing” report is sent foreach device that the RF Receiver does not hear.Fire transmitters have a fixed supervision interval of 4 h.Bosch Security Systems, Inc. | 2/09 | 4998153893-03