Log parameters<br />

Code<br />

Description<br />

ULP3 Parameter name: Supply voltage on fault n-3<br />

Logic address: 7273 = 16#1C69 Type: UINT<br />

CANopen index: 202A/4A Read/write: R<br />

INTERBUS index: 5FB9/9B Unit: 0.1 V<br />

DeviceNet path:<br />

85/01/4A<br />

LCP3 Parameter name: Motor current on fault n-3<br />

Logic address: 7243 = 16#1C4B Type: INT<br />

CANopen index: 202A/2C Read/write: R<br />

INTERBUS index: 5FB9/80 Unit: 0.1 A<br />

DeviceNet path:<br />

85/01/2C<br />

rFP3 Parameter name: Output frequency on fault n-3<br />

Logic address: 7253 = 16#1C55 Type: INT<br />

CANopen index: 202A/36 Read/write: R<br />

INTERBUS index: 5FB9/89 Unit: 0.1 Hz<br />

DeviceNet path: 85/01/36<br />

tHP3 Parameter name: Motor thermal state on fault n-3<br />

Logic address: 7283 = 16#1C73 Type: UINT<br />

CANopen index: 202A/54 Read/write: R<br />

INTERBUS index: 5FB9/A4 Unit: 1<br />

85/01/54 85/01/54<br />

EP3 Parameter name: Status word on fault n-3<br />

Logic address: 7213 = 16#1C2D Type: WORD (bit register)<br />

CANopen index: 202A/E Read/write: R<br />

INTERBUS index: 5FB9/65 Unit: -<br />

DeviceNet path:<br />

85/01/0E<br />

IP3 Parameter name: Extended status word on fault n-3<br />

Logic address: 7223 = 16#1C37 Type: WORD (bit register)<br />

CANopen index: 202A/18 Read/write: R<br />

INTERBUS index: 5FB9/6E Unit: -<br />

DeviceNet path: 85/01/18<br />

CMP3 Parameter name: Command word on fault n-3<br />

Logic address: 7233 = 16#1C41 Type: WORD (bit register)<br />

CANopen index: 202A/22 Read/write: R<br />

INTERBUS index: 5FB9/77 Unit: -<br />

DeviceNet path: 85/01/22<br />