[1.8 FAULT MANAGEMENT] (FLt-)<br />

[OUTPUT PHASE LOSS] (OPL-)<br />

Code<br />

Description<br />

OPL Terminal display: [Output Phase Loss]<br />

Logic address: 9<strong>61</strong>1 = 16#258B Type: WORD (listing)<br />

CANopen index: 2042/C Read/write: R/WS<br />

INTERBUS index: 5FBC/EB Factory setting: 1<br />

DeviceNet path:<br />

91/01/0C<br />

0=[No] (nO): Function inactive<br />

1=[Yes] (YES): Tripping on OPF fault with freewheel stop<br />

2=[Output cut] (OAC): No fault triggered, but management of the output voltage in order to avoid an overcurrent<br />

when the link with the motor is re-established and catch on the fly performed (even if this function has not been<br />

configured).<br />

Odt Terminal display: [OutPh time detect]<br />

Logic address: 7081 = 16#1BA9 Type: UINT<br />

CANopen index: 2028/52 Read/write: R/W<br />

INTERBUS index: 5FBF/07 Unit: 0.11 s<br />

DeviceNet path: 84/01/52 Factory setting: 5<br />

Adjustment range:<br />

5to100<br />

Time delay for taking [Output Phase Loss] (OPL) fault into account.<br />

[INPUT PHASE LOSS] (IPL-)<br />

Code<br />

Description<br />

IPL Terminal display: [Input phase loss]<br />

Logic address: 7002 = 16#1B5A Type: WORD (listing)<br />

CANopen index: 2028/3 Read/write: R/WS<br />

INTERBUS index: 5FBC/86 Factory setting: According to drive rating (1)<br />

DeviceNet path: 84/01/03<br />

0=[Ignore] (nO): Fault ignored, to be used when the drive is supplied via a single phase supply or by the DC bus.<br />

1=[Freewheel] (YES): Fault, with freewheel stop<br />

(1) 0=[Ignore] (nO) for ATV<strong>61</strong>H037M3 to HU75M3, 1 = [Freewheel] (YES) for others.<br />

232