[1.8 FAULT MANAGEMENT] (FLt-)<br />

[THERMAL ALARM STOP] (SAt-)<br />

Code<br />

Description<br />

SAt Terminal display: [Thermal alarm stop]<br />

Logic address: 11021 = 16#2B0D Type: WORD (listing)<br />

CANopen index: 2050/16 Read/write: R/WS<br />

INTERBUS index: 5FBF/3E Factory setting: 0<br />

DeviceNet path: 98/01/16<br />

0=[No] (nO): Function inactive (in this case, the following parameters cannot be accessed)<br />

1=[Yes] (YES): Freewheel stop on drive or motor thermal alarm<br />

tHA Terminal display: [Drv therm. state al]<br />

Logic address: 11009 = 16#2B01 Type: UINT<br />

CANopen index: 2050/A Read/write: R/W<br />

INTERBUS index: 5FBF/38 Unit 1%<br />

DeviceNet path: 98/01/0A Factory setting: 100<br />

Adjustment range<br />

0to118<br />

Thermal state threshold of the drive tripping the deferred stop<br />

ttd Terminal display: [Motor therm. level]<br />

Logic address: 11002 = 16#2AFA Type: UINT<br />

CANopen index: 2050/3 Read/write: R/W<br />

INTERBUS index: 5FBF/33 Unit 1%<br />

DeviceNet path: 98/01/03 Factory setting: 100<br />

Adjustment range<br />

0to118<br />

Thermal state threshold of the motor tripping the deferred stop<br />

ttd2 Terminal display: [Motor2 therm. level]<br />

Logic address: 11006 = 16#2AFE Type: UINT<br />

CANopen index: 2050/7 Read/write: R/W<br />

INTERBUS index: 5FBF/36 Unit 1%<br />

DeviceNet path: 98/01/07 Factory setting: 100<br />

Adjustment range<br />

0to118<br />

Thermal state threshold of the motor 2 tripping the deferred stop<br />

ttd3 Terminal display: [Motor3 therm. level]<br />

Logic address: 11007 = 16#2AFF Type: UINT<br />

CANopen index: 2050/8 Read/write: R/W<br />

INTERBUS index: 5FBF/37 Unit 1%<br />

DeviceNet path: 98/01/08 Factory setting: 100<br />

Adjustment range<br />

0to118<br />

Thermal state threshold of the motor 3 tripping the deferred stop<br />