[1.8 FAULT MANAGEMENT] (FLt-)<br />

[DRIVE OVERHEAT] (OHL-)<br />

Code<br />

Description<br />

OHL Terminal display: [Overtemp fault mgt]<br />

Logic address: 7008 = 16#1B60 Type: WORD (listing)<br />

CANopen index: 2028/9 Read/write: R/WS<br />

INTERBUS index: 5FBC/8A Factory setting: 1<br />

DeviceNet path: 84/01/09<br />

0=[Ignore] (nO): Fault ignored<br />

1=[Freewheel] (YES): Freewheel stop<br />

2=[Per STT] (Stt): Stop according to configuration of [Type of stop] (Stt), see “Stt”, page 194.<br />

4=[fallback spd] (LFF): Change to fallback speed, maintained as long as the fault persists and the run command<br />

has not been removed.<br />

5=[Spd maint.] (rLS): The drive maintains the speed at the time the fault occurred, as long as the fault persists and<br />

the run command has not been removed.<br />

6=[Ramp stop] (rMP): Stop on ramp<br />

7=[Fast stop] (FSt): Fast stop<br />

8=[DC injection] (dCI): DC injection stop<br />

tHA Terminal display: [Drv therm. state al]<br />

Logic address: 11009 = 16#2B01 Type: UINT<br />

CANopen index: 2050/A Read/write: R/W<br />

INTERBUS index: 5FBF/38 Unit 1%<br />

DeviceNet path: 98/01/0A Factory setting: 100<br />

Adjustment range<br />

0to118<br />

Trip threshold for drive thermal alarm (logic output or relay)<br />

233