[1.7 APPLICATION FUNCT.] (FUn-)<br />

[REF. OPERATIONS] (OAI-)<br />

Code<br />

Description<br />

SA2 Terminal display: [Summing ref. 2]<br />

Logic address: 11801 = 16#2E19 Type: WORD (listing)<br />

CANopen index: 2058/2 Read/write: R/WS<br />

INTERBUS index: 5FBD/01 Factory setting: According to CFG (1)<br />

DeviceNet path:<br />

9C/01/02<br />

Selection of a reference to be added to [Ref.1 channel] (Fr1) or [Ref.1B channel] (Fr1b).<br />

0=[No] (nO): No source assigned<br />

1=[AI1] (AI1): Analog input<br />

2=[AI2] (AI2): Analog input<br />

3=[AI3] (AI3): Analog input, if VW3A3202 extension card has been inserted<br />

4=[AI4] (AI4): Analog input, if VW3A3202 extension card has been inserted<br />

163 = [HMI] (LCC): Graphic display terminal<br />

164 = [Modbus] (Mdb): Integrated Modbus<br />

167 = [CANopen] (CAn): Integrated CANopen<br />

169 = [Com. card] (nEt): Communication card (if inserted)<br />

170 = [Prog. card] (APP): Controller Inside card (if inserted)<br />

181 = [RP] (PI): Frequency input, if VW3A3202 extension card has been inserted<br />

182 = [Encoder] (PG): Encoder input, if encoder card has been inserted<br />

SA3 Terminal display: [Summing ref. 3]<br />

Logic address: 11802 = 16#2E1A Type: WORD (listing)<br />

CANopen index: 2058/3 Read/write: R/WS<br />

INTERBUS index: 5FBD/02 Factory setting: 0<br />

DeviceNet path:<br />

9C/01/03<br />

Selection of a reference to be added to [Ref.1 channel] (Fr1) or [Ref.1B channel] (Fr1b).<br />

Possible assignments are identical to [Summing ref. 2] (SA2) above.<br />

dA2 Terminal display: [Subtract ref. 2]<br />

Logic address: 11811 = 16#2E23 Type: WORD (listing)<br />

CANopen index: 2058/C Read/write: R/WS<br />

INTERBUS index: 5FBD/03 Factory setting: 0<br />

DeviceNet path:<br />

9C/01/0C<br />

Selection of a reference to be subtraced from [Ref.1 channel] (Fr1) or [Ref.1B channel] (Fr1b).<br />

Possible assignments are identical to [Summing ref. 2] (SA2) above.<br />

dA3 Terminal display: [Subtract ref. 3]<br />

Logic address: 11812 = 16#2E24 Type: WORD (listing)<br />

CANopen index: 2058/D Read/write: R/WS<br />

INTERBUS index: 5FBD/04 Factory setting: 0<br />

DeviceNet path:<br />

9C/01/0D<br />

Selection of a reference to be subtraced from [Ref.1 channel] (Fr1) or [Ref.1B channel] (Fr1b).<br />

Possible assignments are identical to [Summing ref. 2] (SA2) above.<br />

(1) According to CFG, see “CFG”, page 138.<br />

If CFG = 1: Factory setting = 2<br />

If CFG = 3: Factory setting = 2<br />

Otherwise, factory setting = 0<br />