[1.5 INPUTS / OUTPUTS CFG] (I-O-)<br />

[RP CONFIGURATION] (PLI-)<br />

Code<br />

Description<br />

PIL Terminal display: [RP min value]<br />

Logic address: 13302 = 16#33F6 Type: INT<br />

CANopen index: 2067/3 Read/write: R/WS<br />

INTERBUS index: 5FBD/3F Unit: 0.01 kHz<br />

DeviceNet path: A3/01/67 Factory setting: 0<br />

Adjustment range: - 3000 to 3000<br />

Frequency corresponding to the minimum speed<br />

PFr Terminal display: [RP max value]<br />

Logic address: 13303 = 16#33F7 Type: UINT<br />

CANopen index: 2067/4 Read/write: R/WS<br />

INTERBUS index: 5FBD/40 Unit: 0.01 kHz<br />

DeviceNet path: A3/01/68 Factory setting: 3000<br />

Adjustment range: 0 to 3000<br />

Frequency corresponding to the maximum speed<br />

PFI Terminal display: [RP filter]<br />

Logic address: 13304 = 16#33F8 Type: UINT<br />

CANopen index: 2067/5 Read/write: R/WS<br />

INTERBUS index: 5FBD/41 Unit: 1ms<br />

DeviceNet path: A3/01/69 Factory setting: 0<br />

Adjustment range: 0 to 1000<br />

Interference filtering<br />