Log parameters<br />

Code<br />

Description<br />

ULP4 Parameter name: Supply voltage on fault n-4<br />

Logic address: 7274 = 16#1C6A Type: UINT<br />

CANopen index: 202A/4B Read/write: R<br />

INTERBUS index: 5FB9/9C Unit: 0.1 V<br />

DeviceNet path:<br />

85/01/4B<br />

LCP4 Parameter name: Motor current on fault n-4<br />

Logic address: 7244 = 16#1C4C Type: INT<br />

CANopen index: 202A/2D Read/write: R<br />

INTERBUS index: 5FB9/81 Unit: 0.1 A<br />

DeviceNet path:<br />

85/01/2D<br />

rFP4 Parameter name: Output frequency on fault n-4<br />

Logic address: 7254 = 16#1C56 Type: INT<br />

CANopen index: 202A/37 Read/write: R<br />

INTERBUS index: 5FB9/8A Unit: 0.1 Hz<br />

DeviceNet path: 85/01/37<br />

tHP4 Parameter name: Motor thermal state on fault n-4<br />

Logic address: 7284 = 16#1C74 Type: UINT<br />

CANopen index: 202A/55 Read/write: R<br />

INTERBUS index: 5FB9/A5 Unit: 1<br />

85/01/55 85/01/55<br />

EP4 Parameter name: Status word on fault n-4<br />

Logic address: 7214 = 16#1C2E Type: WORD (bit register)<br />

CANopen index: 202A/F Read/write: R<br />

INTERBUS index: 5FB9/66 Unit: -<br />

DeviceNet path:<br />

85/01/0F<br />

IP4 Parameter name: Extended status word on fault n-4<br />

Logic address: 7224 = 16#1C38 Type: WORD (bit register)<br />

CANopen index: 202A/19 Read/write: R<br />

INTERBUS index: 5FB9/6F Unit: -<br />

DeviceNet path: 85/01/19<br />

CMP4 Parameter name: Command word on fault n-4<br />

Logic address: 7234 = 16#1C42 Type: WORD (bit register)<br />

CANopen index: 202A/23 Read/write: R<br />

INTERBUS index: 5FB9/78 Unit: -<br />

DeviceNet path: 85/01/23<br />