[1.7 APPLICATION FUNCT.] (FUn-)<br />

Code<br />

Description<br />

IdC2 Terminal display: [DC inject. level 2]<br />

Logic address: 11212 = 16#2BCC Type: UINT<br />

CANopen index: 2052/D Read/write: R/W<br />

INTERBUS index: 5FBF/43 Unit: 0.1 A<br />

DeviceNet path: 99/01/0D Factory setting: 0.5 In (1)<br />

Adjustment range: 0.1 In to 1.41 In (1)<br />

Injection current activated by logic input or selected as stop mode, once period of time [DC injection time 1] (tdI) has elapsed.<br />

tdC Terminal display: [DC injection time 2]<br />

Logic address: 11211 = 16#2BCB Type: UINT<br />

CANopen index: 2052/C Read/write: R/W<br />

INTERBUS index: 5FBF/42 Unit: 0.1 s<br />

DeviceNet path: 99/01/0C Factory setting: 5<br />

Adjustment range: 1 to 300<br />

Maximum current injection time [DC inject. level 2] (IdC2)<br />

(1) In corresponds to the rated drive current indicated in the installation manual and on the drive nameplate.<br />