[1.7 APPLICATION FUNCT.] (FUn-)<br />

[AUTO DC INJECTION] (AdC-)<br />

Code<br />

Description<br />

AdC Terminal display: [Auto DC injection]<br />

Logic address: 10401 = 16#28A1 Type: WORD (listing)<br />

CANopen index: 204A/2 Read/write: R/W<br />

INTERBUS index: 5FBF/2D Factory setting: 1<br />

DeviceNet path: 95/01/02<br />

0=[No] (nO): No injection<br />

1=[Yes] (YES): Adjustable injection time<br />

2=[Continuous] (Ct): Continuous standstill injection<br />

tdC1 Terminal display: [Auto DC inj. time 1]<br />

Logic address: 10402 = 16#28A2 Type: UINT<br />

CANopen index: 204A/3 Read/write: R/W<br />

INTERBUS index: 5FBF/2E Unit: 0.1 s<br />

DeviceNet path: 95/01/03 Factory setting: 5<br />

Standstill injection time.<br />

SdC2 Terminal display: [Auto DC inj. level 2]<br />

Adjustment range: 1 to 300<br />

Logic address: 10405 = 16#28A5 Type: UINT<br />

CANopen index: 204A/6 Read/write: R/W<br />

INTERBUS index: 5FBF/31 Unit: 0.1 A<br />

DeviceNet path: 95/01/06 Factory setting: 0.5 In (1)<br />

2 nd level of standstill DC injection current.<br />

tdC2 Terminal display: [Auto DC inj. time 2]<br />

Adjustment range: 0 to 1.2 In (1)<br />

Logic address: 10404 = 16#28A4 Type: UINT<br />

CANopen index: 204A/5 Read/write: R/W<br />

INTERBUS index: 5FBF/30 Unit: 0.1 s<br />

DeviceNet path: 95/01/05 Factory setting: 0<br />

2 nd standstill injection time.<br />

Adjustment range: 0 to 300<br />

(1) In corresponds to the rated drive current indicated in the installation manual and on the drive nameplate.<br />