[1.1 SIMPLY START] (SIM-)<br />

Code<br />

Description<br />

CFG Terminal display: [Macro configuration]<br />

Logic address: 3052 = 16#BEC Type: WORD (listing)<br />

CANopen index: 2000/35 Read/write: R/WS<br />

INTERBUS index: 5FBC/07 Factory setting: 0<br />

DeviceNet path: 70/01/35<br />

0=[Start/Stop] (StS): Start/stop<br />

1=[M. handling] (HdG): Material handling<br />

2=[Hoisting] (HSt): Hoisting<br />

3=[Gen. Use] (GEn): General use<br />

4=[PID regul.] (PId): PID regulation<br />

5=[Network C.] (nEt): Communication bus<br />

6=[Mast./slave] (MSL): Master/slave<br />

CCFG Terminal display: [Customized macro]<br />

Logic address: 3053 = 16#BED Type: WORD (listing)<br />

CANopen index: 2000/36 Read/write: R<br />

INTERBUS index:<br />

5FB9/02<br />

DeviceNet path: 70/01/36<br />

1=[Yes] (YES): Read-only parameter<br />