[1.4 MOTOR CONTROL] (drC-)<br />

Code<br />

Description<br />

OFI Terminal display: [Sinus filter]<br />

Logic address: 3109 = 16#C25 Type: WORD (listing)<br />

CANopen index: 2001/A Read/write: R/WS<br />

INTERBUS index: 5FBC/0B Factory setting: 0<br />

DeviceNet path:<br />

70/01/6E<br />

0=[No] (nO): No sinus filter<br />

1=[Yes] (YES): Use of a sinus filter, to limit overvoltages on the motor and reduce the ground fault leakage current.<br />

SFr Terminal display: [Switching freq.]<br />

Logic address: 3102 = 16#C1E Type: UINT<br />

CANopen index: 2001/3 Read/write: R/W<br />

INTERBUS index: 5FBF/02 Unit: 0.1 kHz<br />

DeviceNet path: 70/01/67 Factory setting: 25 or 40 according to drive<br />

rating<br />

Switching frequency<br />

CLI Terminal display: [Current Limitation]<br />

Adjustment range: 10 to 160<br />

Logic address: 9201 = 16#23F1 Type: UINT<br />

CANopen index: 203E/2 Read/write: R/W<br />

INTERBUS index: 5FBF/28 Unit: 0.1 A<br />

DeviceNet path: 8F/01/02 Factory setting: 1.5 In (1)<br />

First current limitation<br />

nrd Terminal display: [Noise reduction]<br />

Adjustment range: According to SFr (2)<br />

Logic address: 3107 = 16#C23 Type: WORD (listing)<br />

CANopen index: 2001/8 Read/write: R/WS<br />

INTERBUS index: 5FBC/09 Factory setting: 1<br />

DeviceNet path:<br />

70/01/6C<br />

0=[No] (nO): Fixed frequency<br />

1=[Yes] (YES): Frequency with random modulation<br />

SUL Terminal display: [Motor surge limit.]<br />

Logic address: 12601 = 16#3139 Type: WORD (listing)<br />

CANopen index: 2060/2 Read/write: R/WS<br />

INTERBUS index: 5FBD/1F Factory setting: 0<br />

DeviceNet path:<br />

A0/01/02<br />

This function limits motor overvoltages.<br />

0=[No] (nO): Function inactive<br />

1=[Yes] (YES): Function active<br />

(1) In corresponds to the rated drive current indicated in the installation manual and on the drive nameplate.<br />

(1) According to SFr, see above.<br />

If SFr ≥ 20: Adjustment range = 0 to 1.65 In (1)<br />

If SFr < 20: Adjustment range = 0 to 1.36 In (1)<br />

154