Forced local mode<br />

Definition<br />

Forced local mode supports switching to the terminals or display terminal.<br />

This function complements channel switching and makes it possible to make use of an existing function from the <strong>Altivar</strong> 58 range.<br />

Forced local mode is only available in DSP402 profile, not in I/O profile.<br />

All other communication takes priority over forced local mode.<br />

Forced local mode can be configured via the display terminal:<br />

Menu<br />

Submenu<br />

[1.9 COMMUNICATION] (COM-) [FORCED LOCAL] (LCF-)<br />

Parameter<br />

Forced local switch<br />

[Forced local assign.] (FLO)<br />

Forced local channel<br />

[Forced local Ref.] (FLOC)<br />

Possible values<br />

Function inactive:<br />

[No] (nO)<br />

Assignment to a logic input (LI1 ... LI14):<br />

[LI1] (LI1) ... [LI14] (LI14)<br />

Forced local mode is active when the input is at state 1.<br />

Forced local on stop.<br />

[No] (nO)<br />

Assignment of the command to the terminals and of the reference to one of the analog inputs<br />

AI1 ... AI4<br />

[AI2 ref.] (AI2), [AI3 ref.] (AI3), [AI4 ref.] (AI4)<br />

Assignment of the command to the terminals and of the reference to the frequency input (if card<br />

present)<br />

[Pulse Input] (PI)<br />

Assignment of the reference [HMI Frequency ref.] (LFr) and of the command<br />

(RUN/STOP/FWD/REV buttons) to the graphic display terminal<br />

[HMI] (LCC)<br />

In "forced local" state:<br />

• Any attempts to write the parameter via one of these channels is rejected (applies to command, reference and adjustment<br />

parameters).<br />

• However, the parameters can be read.<br />

• The drive does not register a communication fault.<br />

On exiting "forced local" mode:<br />

• The drive copies the run commands, the direction and the forced local reference to the active channel (maintained).<br />

• Monitoring of the active command and reference channels resumes following a time delay [Time-out forc. local] (FLOt).<br />

• Drive control only takes effect once the drive has received the reference and the command.<br />

The time delay [Time-out forc. local] (FLOt) (default value = 10 s) can be configured via the remote graphic display terminal:<br />

Menu Submenu Parameter<br />

[1.9 COMMUNICATION] (COM-) [FORCED LOCAL] (LCF-) [Time-out forc. local] (FLOt)<br />