[1.4 MOTOR CONTROL] (drC-)<br />

Code<br />

Description<br />

rSM Terminal display: [Stator R measured]<br />

Logic address: 9640 = 16#25A8 Type: UINT<br />

CANopen index: 2042/29 Read/write: R<br />

INTERBUS index: 5FB9/E0 Unit: According to drive rating (1)<br />

DeviceNet path: 91/01/29 Adjustment range: 0 to 65,535<br />

Cold stator resistance, calculated by the drive.<br />

IdM Terminal display: [Idr]<br />

Logic address: 9650 = 16#25B2 Type: UINT<br />

CANopen index: 2042/33 Read/write: R<br />

INTERBUS index: 5FB9/E1 Unit: 0.1 A<br />

DeviceNet path: 91/01/33 Adjustment range: 0 to 65,535<br />

Magnetizing current, calculated by the drive.<br />

LFM Terminal display: [Lfr]<br />

Logic address: 9660 = 16#25BC Type: UINT<br />

CANopen index: 2042/3D Read/write: R<br />

INTERBUS index: 5FB9/E2 Unit: 0.01 mH<br />

DeviceNet path: 91/01/3D Adjustment range: 0 to 65,535<br />

Leakage inductance in mH, calculated by the drive.<br />

trM Terminal display: [T2r]<br />

Logic address: 9665 = 16#25C1 Type: UINT<br />

CANopen index: 2042/42 Read/write: R<br />

INTERBUS index: 5FB9/E3 Unit: 1ms<br />

DeviceNet path: 91/01/42 Adjustment range: 0 to 65,535<br />

Rotor time constant in ms, calculated by the drive.<br />

nSL Terminal display: [Nominal motor slip]<br />

Logic address: 9605 = 16#2585 Type: UINT<br />

CANopen index: 2042/6 Read/write: R<br />

INTERBUS index: 5FB9/DE Unit: 0.1 Hz<br />

DeviceNet path: 91/01/06 Adjustment range: 0 to 65,535<br />

Rated slip in Hz, calculated by the drive.<br />

(1) According to drive rating<br />

If Power > 75 kW: Unit = 1 µΩ<br />

If Power ≤ 75 kW: Unit = 1 mΩ<br />