[1.4 MOTOR CONTROL] (drC-)<br />

Code<br />

Description<br />

(1) According to bFr, see “bFr”, page 142.<br />

If bFr = 0: Factory setting: 500<br />

If bFr = 1: Factory setting: 600<br />

(2) According to bFr, see “bFr”, page 142.<br />

If bFr = 0: Factory setting: 600<br />

If bFr = 1: Factory setting: 720<br />

tUS Terminal display: [Auto tuning status]<br />

Logic address: 9609 = 16#2589 Type: WORD (listing)<br />

CANopen index: 2042/A Read/write: R<br />

INTERBUS index: 5FC5/1C Factory setting: 0<br />

DeviceNet path:<br />

91/01/0A<br />

0=[Not done] (tAb): The default stator resistance value is used to control the motor.<br />

1=[Pending] (PEnd): Auto-tuning has been requested but not yet performed.<br />

2=[In Progress] (PrOG): Auto-tuning in progress.<br />

3=[Failed] (FAIL): Auto-tuning has failed.<br />

4=[Done] (dOnE): The stator resistance measured by the auto-tuning function is used to control the motor.<br />

5=[Customized] (CUS): Auto-tuning has been performed, but at least one parameter set by this auto-tuning<br />

operation has subsequently been modified.<br />

PHr Terminal display: [Output Ph rotation]<br />

Logic address: 13401 = 16#3459 Type: WORD (listing)<br />

CANopen index: 2068/2 Read/write: R/WS<br />

INTERBUS index: 5FBD/45 Factory setting: 0<br />

DeviceNet path:<br />

A4/01/02<br />

0=[ABC] (AbC): Forward<br />

1=[ACB] (ACb): Reverse<br />

This parameter can be used to reverse the direction of rotation of the motor without reversing the wiring.<br />

Ctt Terminal display: [Motor control type]<br />

Logic address: 9607 = 16#2587 Type: WORD (listing)<br />

CANopen index: 2042/8 Read/write: R/WS<br />

INTERBUS index: 5FC2/06 Factory setting: 0<br />

DeviceNet path: 91/01/08<br />

0=[SVC V] (UUC): Open-loop voltage flux vector control<br />

1=[SVC I] (CUC): Open-loop current flux vector control<br />

2=[FVC] (FUC): Closed-loop current flux vector control for motor with incremental encoder type sensor<br />

3=[V/F 2pts] (UF2): Simple V/F profile without slip compensation<br />

4=[V/F 5pts] (UF5): 5-segment V/F profile<br />

5=[Sync. mot.] (SYn): For synchronous permanent magnet motors with sinusoidal electromotive force (EMF) only<br />

U0 Terminal display: [U0]<br />

Logic address: 12401 = 16#3071 Type: UINT<br />

CANopen index: 205E/2 Read/write: R/WS<br />

INTERBUS index: 5FBD/14 Unit: 1V<br />

DeviceNet path: 9F/01/02 Factory setting: 0<br />

V/f ratio<br />

Adjustment range:<br />

0to600<br />

144